4-23
n61
Stop Key Selection
Setting range
0, 1
Factory setting 0
•
When inputting Inverter operation from the control terminals, the Stop Key on the Digi-
tal Operator can be set to “enabled” or “disabled.”
Value
Description
0
Stop Key enabled
1
Stop Key disabled
Note 1. When operating the Inverter from the Digital Operator, the Stop Key is always
enabled irrespective of its setting.
Note 2. This constant is available for models with a PROM number (software version)
of “200” or higher.
n64
Operator’s Frequency Setting Method
Setting range
0, 1
Factory setting 0
•
Used for setting the frequency from the Digital Operator.
•
Select the Enter Key operation when setting the frequency command from the Digital
Operator.
Value
Description
0
Enter Key required for changing frequency
1
Enter Key not required for changing frequency (may be changed using
Increment and Decrement Keys.)
n68
Error History
This constant can only be displayed. It cannot be set.
•
Information about the last error is recorded in this constant. Use this information for
troubleshooting purposes.
•
The display format is as follows:
Error code
8.8.8.
Note This constant is available for models with a PROM number (software version) of
“220” or higher.
Preparing for Operation
Chapter 4
Содержание SYSDRIVE 3G3EV SERIES
Страница 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Страница 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Страница 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 32: ...Chapter 4 Preparing for Operation 4 1 Preparation Procedure 4 2 Using the Digital Operator 4 3 Test Run 4...
Страница 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...