3 Initial Setting
3 - 18
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
3-4
Registering the Initial Settings and
Sensor Configuration of the Main Unit
(Setting K6PM screen)
Before using a Main Unit, it is necessary to register the initial settings of the Main Unit as well as the
sensor configuration in the Main Unit.
Registration must be performed after confirming that angle deviation has not occurred in all infrared
thermal sensors.
Initial Settings of the Main Unit
Set the following items when making the initial settings of the Main Unit.
Sensor Configuration
When power is supplied, the Main Unit automatically searches the connected infrared thermal sensors.
After confirming the search results as the sensor configuration, it is necessary to register them to the
Main Unit if they are correct.
If the sensor configuration is not correct, check the connection between the Main Unit and each infrared
thermal sensor, and also each K6PM-TH sensor number setting
*1
. Thereafter, again turn ON the power
supply to the Main Unit, and check the current sensor configuration.
*1. The setting depends on the DIP switch pin on the side surface of the infrared thermal sensor. For details, refer
The method using the software tool is described below.
1
After selecting the Main Unit on the Device List of K6PM screen, click the
Setting
Button. The
Setting K6PM screen will be displayed.
2
In the Setting parameters group box, select the
option
Button of each setting item.
3
Check the sensor number, connection status, and position setting.
Item
Description
Value
Reference destination of function
details
Temperature
unit
On the Main Unit front-panel,
select whether to display the
temperature in °C or °F.
°C (default), °F
---
Alarm latch
Select whether to use the func-
tion for latching the alarm status
of the comprehensive alarm
(threshold 1 or 2).
ON: Use (default)
OFF: Not used
page 4-16 of
Monitoring the Temperature in Con-
trol Panel with the Main Unit and the
Software Tool
Output inversion Set the logic of the transistor out-
put method of the comprehen-
sive alarm.
ON: Normally open
OFF: Normally
closed (default)
Transistor Output Type of the Main
Unit
Use Running
Time
Select whether or not to use the
Notification of the Main Unit
Replacement Timing.
ON: Use
OFF: Not used
(default)
Maintenance Forecast Monitor
Function
on page 4-17 of same as
above
Use arrival
prediction
Select whether or not to use the
Temperature arrival prediction.
ON: Use
OFF: Not used
(default)
on page 4-15 of
same as above
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......