![Omron K6PM-TH Скачать руководство пользователя страница 162](http://html1.mh-extra.com/html/omron/k6pm-th/k6pm-th_user-manual_743374162.webp)
Appendices
A - 6
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
Measured Value Display
Measurement level
Methods for checking
Main Unit (display)
Software tool
Communications
Temperature of each seg-
ment and sensor internal
temperature
The segment display of
each sensor can be
switched on the Main
Unit front-panel.
Can be checked on the
Monitoring sensor screen.
• EtherNet/IP tag data
link communications
• EtherNet/IP mes-
sage communica-
tions
• Modbus TCP com-
munications
Differential temperature per
segment from the K6PM-TH
sensor internal temperature
Not supported
Not supported
Not supported
Temperature of each infra-
red thermal sensor
Not supported
The past maximum value
can be monitored on the
Monitoring K6PM
Screen.
Not supported
Temperature of each pixel
Not supported
The temperature can be
displayed when the cur-
sor is placed on the ther-
mal image on the
Monitoring sensor
Screen.
• EtherNet/IP mes-
sage communica-
tions
• Modbus TCP com-
munications
Alarms of each Main Unit
(Alarms of all infrared ther-
mal sensors connected to
the Main Unit)
The occurrence of an
alarm can be checked
on the alarm bar.
The occurrence of an
alarm can be checked on
the
Device List of K6PM
Screen.
The occurrence of an
alarm can be checked
from the Main Unit sta-
tus.
A-1-2
Infrared Thermal Sensor
Infrared Thermal Sensor Ratings
Model
K6PM-THS3232
Item
Power
supply
Power supply voltage
24 VDC
Allowable operating voltage range
85% to 110% of the power supply voltage
Power supply frequency range
---
Power consumption
0.4 W max./Unit at 24 VDC
*1
Ambient operating temperature
-10 to +55°C (with no condensation or freezing)
Storage temperature
-20 to +65°C (with no condensation or freezing)
Ambient operating humidity
25% to 85% (with no condensation)
Storage humidity
25% to 85% (with no condensation)
Exterior color
Black
Case material
PC UL94-V0
Altitude
2,000 m max.
Applicable wires
Stranded wires or solid wires
Applicable wire size
0.25 to 1.5 mm
2
(AWG24 to AWG16)
Current capacity
8 A (per pole)
Weight
50 g max.
Mounting
Mounting
*2
Screw Mounting
Dimensions
43 × 60 × 25.1 mm (W×H×D) Terminals not included
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......