7 - 3
7 Troubleshooting
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
7-1 Main
Unit
7
Measure-
ment val-
ues are
not dis-
played.
MS blinks red
and running
time error is ON
in the device
status.
The hardware used
for the replacement
time alert function
may have failed.
Cycle the K6PM power off and
then on.
If the error still occurs, contact
OMRON sales or your dealer.
MS indicator is
lit red.
The Main Unit may
be damaged.
Turn ON the power supply to the
Main Unit again. If it still occurs,
contact our sales or distributor.
---
The current temperature is
displayed, but MS blinks red
and K6PM sensor error is
ON in the K6PM device sta-
tus.
A K6PM-TH sensor
angle deviation has
occurred.
Return the sensor angle to its
original state.
Alternatively, perform position
adjustment and position registra-
tion.
If the event cannot be cleared
with the above action, turn ON
the power supply to the sensor
again.
This event may be cleared by
turning ON the power supply to
the sensor multiple times.
If no improvement is seen in the
event after taking the above
action, replace the sensor.
4-13
Refer to K6PM-TH sen-
sor location registration
or K6PM-TH sensor
angle deviation notifica-
tion function.
Refer to
Take When Angle Devi-
ation Occurs
7-5 described later.
The current temperature
value is displayed, but
"AGE" lights up.
The Main Unit run-
ning time has
reached the
approximate
replacement time.
Consider replacing the Main Unit.
4-13
Refer to the Notification
of the Main Unit
replacement timing.
The mea-
sured
value dis-
played is
incorrect.
The measured
value is fixed
and does not
change
In the case of a
trigger (external
trigger), the mea-
sured value is held
and displayed.
Either turn ON the power again or
turn OFF the external trigger
input.
4-13
Refer to External trigger
input of the Main Unit.
Transistor
output 1, 2
Transistor out-
put 1 or 2 does
not return
during measur-
ing and moni-
toring despite
the measured
value that com-
prehensive
alarm should be
normal.
Alarm latch is set
to "enable"
Long-press the SEG / ALMRST
key on the front panel of the
K6PM device for at least 5 sec-
onds to release the alarm latch.
Or, change the alarm latch setting
to None (Disabled).
4-13
Refer to Alarm latch of
the Main Unit.
Problems
Cause
Possible correction
Reference
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......