1 Outline
1 - 12
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
Transistor Output
The Main Unit has the following operating modes.
There are the following two operating modes before registering the configuration of the infrared thermal
sensors.
K6PM-TH Sensor Search Mode
In this mode, the Main Unit automatically searches for the connected infrared thermal sensors when
the power supply is turned ON or when the software is reset, and decides the configuration of the
infrared thermal sensors.
The search results can be checked on the Setting K6PM screen of the software tool (for details,
refer to
3-4 Registering the Initial Settings and Sensor Configuration of the Main Unit (Setting K6PM
K6PM-TH Sensor Position Adjustment Mode
In this mode, communications are performed with only one fixed infrared thermal sensor in order to
perform position adjustment of the infrared thermal sensor.
When you switch to the Setting K6PM screen with the software tool, the Main Unit automatically
switches to this mode (for details, refer to
3-3 Registering the Sensor Position (Setting sensor
Name
Description
Transistor output 1
Threshold 1 excess
output of comprehen-
sive alarm.
Transistor output type
can be set to Normally
Closed or Normally
Open.
When the "Transistor output type" is set to "Normally closed":
If threshold 1 exceeded occurs for the comprehensive alarm,
transistor output remains OFF and transistor output 2
remains ON.
If threshold 2 exceeded occurs for the comprehensive alarm,
both transistor output and transistor output 2 turn OFF.
(By default, it is set to "Normally closed". By setting it to "Nor-
mally open" with the software tool, ON/OFF can be reversed.)
Transistor output 2
Threshold 2 excess
output of comprehen-
sive alarm. Transistor
output type can be set
to Normally Closed or
Normally Open.
Transistor output 3
Main Unit error and K6PM-TH sensor error output
• Normal: ON
• Main Unit error and K6PM-TH sensor error: OFF
Note 1: The Main Unit error and K6PM-TH sensor error specify any one of the following:
• Main Unit internal error (internal CPU error or internal memory error)
• K6PM-TH sensor communications error or sensor type error
• The detection of the K6PM-TH sensor angle deviation
• Temperature measurement range exceeded
• Running time error
Note 2: The output type of transistor 3 is fixed as Normally closed.
1-4-2
Operating Modes of the Main Unit
Before Registering the Configuration of the Infrared Thermal Sen-
sors
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......