![Omron K6PM-TH Скачать руководство пользователя страница 112](http://html1.mh-extra.com/html/omron/k6pm-th/k6pm-th_user-manual_743374112.webp)
5 Monitoring and Setting with the EtherNet/IP Communications
5 - 10
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
5-3
Monitoring and Setting Using the CIP
Message Communications and
Examples of Communications
Instructions
This section shows the contents of monitoring and setting using the CIP message communications and
examples of communications instructions.
The services supported by the objects in Main Unit are as follows.
This object reads the Main Unit status and number of connected K6PM-TH sensors.
Specify 374 hex.
Specify 01 hex.
5-3-1
Services Supported by Objects in Main Units
Object name
Class ID
Function
Main Unit monitor
object
374 hex
This object reads the Main Unit status and number of connected
K6PM-TH sensors.
K6PM-TH sensor moni-
tor object
375 hex
This object reads the status of each sensor of the Main Unit and the cur-
rent temperature value of each segment.
K6PM-TH sensor tem-
perature monitor object
376 hex
This object reads the current temperature value of each pixel of each sen-
sor of the Main Unit.
Main Unit setting object
377 hex
This object writes the setting parameters (such as the existence of alarm
latch, transistor output method, enabling or disabling of "Use predicted
arrival time", etc.) of the Main Unit. Alternatively, it performs each opera-
tion instruction (such as K6PM-TH sensor registration, K6PM-TH sensor
location registration, reset of the maximum temperature of all sensors
connected to the corresponding Main Unit, etc.).
K6PM-TH sensor alarm
setting object
378 hex
This object writes the temperature alarm parameter of each sensor of the
Main Unit.
Identity Object
01 hex
This object reads the Main Unit software reset and the Main Unit identifi-
cation information, and also reads the state of the built-in EtherNet/IP
port.
TCP/IP Interface object
F5 hex
This object reads and writes settings such as the IP address, subnet
mask, default gateway, etc.
5-3-2
Main Unit Monitor Object (Class ID: 374 hex)
Service Codes
Service code
Service name
Description
Supported services
Classes
Instances
01 hex
Get_Attributes_All
Reads the values of all attributes.
Not supported
Supported
0E hex
Get_Attribute_Single Reads the value of the specified attribute.
Not supported
Supported
Class ID
Instance ID
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......