3-2 Main Unit Monitor Object (Class ID
: 374 hex)
The attribute ID specifies the information to read.
Class Attribute ID
None
Instance Attribute ID
The instance attribute ID specifies the per-instance attribute.
An example of a case where the instance ID is 01 hex is described below.
• Main Unit status
Attribute ID
Attribute ID
Parameter name
Description
Attri-
bute
Data
Data type
64 hex
Main Unit status
Refer to
on page 5-11 described
later.
Read
UINT
65 hex
Running time data
Running time ratio
0 to 100% (0000 hex to 0064 hex)
Read
UINT
66 hex
Software version
Software version
Set as desired by a double-byte BCD expression.
Example: 0110 hex for V1.10
Read
UINT
67 hex
Number of connected
K6PM-TH sensors
0 to 31
(0000 to 001F hex)
Read
UINT
68 hex
Target sensor in posi-
tion adjustment mode
0: No target sensor in position adjustment mode
1: K6PM-TH sensor 1 position adjustment mode
···:
31: K6PM-TH sensor 31 position adjustment mode
(0000 to 001F hex)
Read
UINT
Bit position
Status
Bit contents
0
1
0
Main Unit internal error
Not occurred
Occurred
1
K6PM-TH sensor error
*1
*1. When any one of a K6PM-TH sensor communications error, sensor type error, K6PM-TH sensor angle devia-
tion error, and temperature measurement range exceeded occurs in any of the sensors connected to the Main
Unit.
Not occurred
Occurred
2
Running time error
*2
Not occurred
Occurred
3
Running time reaches 100%.
Unreached
Reached
4
monitoring mode
Stop
Execute
5
K6PM-TH sensor search mode
Stop
Execute
6
K6PM-TH sensor position adjustment mode
Stop
Execute
7
Interruption of temperature measurement
Not occurred
Occurred
8
comprehensive temperature alarm (threshold 1 exceeded)
Not occurred
Occurred
9
comprehensive temperature alarm (threshold 2 exceeded)
Not occurred
Occurred
10
Reserved
11
Reserved
12
Reserved
13
TR 1 (transistor 1 output state)
OFF
ON
14
TR 2 (transistor 2 output state)
OFF
ON
15
TR 3 (transistor 3 output state)
OFF
ON
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......