Operation manual
G9SR
Page 62 of 79
11.2
Wiring examples G9SR-
AD□
-
□ unit
11.2.1
G9SR-
AD□
-
□
in E-Stop application up to PLe
Settings G9SR-AD:
•
Manual Restart enabled
•
EDM enabled
•
Dynamic Input Test enabled
Dip switch settings: 1
2
3
4
5
6
7
8
OFF ON
ON
OFF OFF OFF OFF OFF
Description:
E-Stop pushbutton connected to T12 and T22
Restart pushbutton connected to T31
KM1 and KM2: Motor Contactors
Feedback loop (EDM) connected to T32
Remarks:
This setup can also be used with safety limit switches and key operated door switches.
For door and gate monitoring applications please consider the requirements from ISO
14119.
Wiring is using the dynamic test pulses.
Applicable up to PLe acc. EN ISO 13849-1 (electrical system).
Motor circuit (contacts of KM1 and KM2) not shown.