10
Combining G9SR units
The G9SR-
AD□
-
□ unit can be combined with G9SR
-
BC□
-
□ and G9SR
-
EX□
-T90-
□
units.
Combinations possible are:
1)
Extending a G9SR-AD with up to two G9SR-BC to create an input loop.
See also § 10.1
on page 49
2)
Extending a G9SR-AD with up to three G9SR-EX to create an output loop.
See also § 10.2
on page 50
3)
Extending a G9SR-AD with up to two G9SR-BC plus up to three G9SR-EX.
This creates an input loop and an output loop.
See also § 10.3
on page 51
Caution!
Use a single power supply for AD and EX units.
For BC units separate power supplies can be used connecting the 0V of all power
supplies together.
Below an example of G9SR system with multi power supplies connections
G9
SR-AD
G9SR-EX
G9SR-EX
G9SR-EX
T42 T41
OMRON
S8VK-G03024
A1 A2
A1 A2
T43 T44 T42 T41
+ -
G9SR-BC
G9SR-BC
OMRON
S8VK-G03024
+ -
OMRON S8VK-G03024
+ -
A1 A2
A1 A2
T32 14
T32 14
A1 A2
A1 A2
T42 T41
T42 T41
Max 20 mt.
Max 20 mt.
Common 0V