manualshive.com logo in svg
background image

TM

CURRENT MONITORING

INSTALLATION GUIDE

Installer’s Specifications

Sensor Power 

Induced from monitored conductor

Amperage Range 

0.5 to 200 A continuous

Insulation Class 

600 VAC RMS

Frequency Range 

50/60 Hz

Temperature Range -15° to 60°C (5° to 140°F)

Humidity Range 

10-90% RH non-condensing

Relay Coil 

24 VAC/DC; 10 mA

Relay Contact 

8(3.5) A@250 VAC/DC, 30 VDC, 1/4 HP

Status Output 

N.O. 1.0 A@30 VAC/DC

Off-State Resistance 

0 (open switch represents >1 MΩ)

Terminal Block Max. Wire Size 

14 AWG

Terminal Block Torque (nom.) 

4 in-lbs (0.45 N-m)

Agency Approvals 

UL508 E150462

The product design provides for basic insulation only. 

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. 

See NFPA 70E in the USA, or applicable local codes.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Use a properly rated voltage sensing device to confirm power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
•  Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

Wiring ExamplE

H740

TM

740

DimEnsions

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

installation

Disconnect and lock out power to the enclosure containing the 

conductor to be monitored.

1.  Locate a mounting surface for the removable mounting bracket that will allow 

the monitored conductor to pass through the center window when it is installed 
and that will keep the device at least 1/2” from any uninsulated conductors. 
Determine cable routing for the controller connection, allowing wiring to reach 
the mounting location.

2.  Drill holes to mount the bracket to the chosen surface using the included screws.

3.  Wire the output connections and relay between the sensor and the controller 

(solid-state contact).

4.  Wire sensor to control power.

5.  Route the conductor through the sensor’s center window and slip the assembly 

into the mounting bracket.

6.  Secure enclosure and reconnect power.

0.2” x 0.15”

slot (2x)

1.1" 

(27 mm)

2.8"

(68 mm)

0 0.7"

(19 mm)

0.9"

(23 mm)

3.0" 

(75 mm)

Removable/Adjustable Mounting Bracket

3.8"

(95 mm)

4.2"

(106 mm)

Fan or Pump

Digital Control

DI 

(Status)

DO 

(Relay

          Coil)

Control 

Power

730

RELAY COIL

1.0A@30 VAC/D

C

STATUS 

OUTPUT 

24VAC/DC

* Observe this polarity 

when connecting the 

relay coil to DC Voltage.

RELAY COIL

Motor

CONTACTOR

www.

.com

[email protected]

1.800.561.8187

Отзывы: