Operation manual
G9SR
Page 10 of 79
4
Technical specifications
4.1
General specifications
Item
Value
Mounting
DIN rail
Housing Material & Connectors
Plastic (grey)
Dimensions, see page 3
Connectors
Removable cage clamp terminals
Operating temperature range
-10°C to + 55°C
Storage temperature range
-25°C to + 70°C
Humidity
0 to 95% RH. No icing or condensation
Enclosure rating (EN 60529)
IP20 (mount in a IP54 cabinet or higher
according to IEC/ EN 60529 )
Resistance to
Vibration (to IEC 68-2-6)
Shock (to IEC 68-2-27)
0,375mm 10 to 70 Hz
30G 18ms
Operating voltage
24V DC ± 20%
Current consumption
excluding auxiliary output
<0.15A
Minimum EDM and RESTART
input current
6mA
Minimum EDM and RESTART
voltage for an ON signal
19V DC
Minimum voltage for T12 and
T22 for an ON signal
17V DC
Minimum input current for T12
and T22
6mA
Maximum T12, T22, EDM and
RESTART voltage for an OFF
signal
11V DC
Power-ON delay
< 2 sec.
Outputs static
G9SR-BC Output voltage High
G9SR-BC Output voltage Low
2A continuous for OSSD
0.5A for Auxiliary output
Unit supply voltage -1V
0V
Output relay on –AD and -EX
Max. 4A AC1*
Max. 5A AC15
Max. 4A DC1*
Max. 5A DC13
*
See also § 4.2
Содержание G9SR
Страница 1: ...ZX T Series Cat No J12E EN 03 G9SR Safety Relays OPERATION MANUAL G9SR BC G9SR AD G9SR EX...
Страница 34: ...Operation manual G9SR Page 8 of 79 3 1 Test the OFF behaviour...
Страница 35: ...Operation manual G9SR Page 9 of 79 3 2 Test the ON behaviour...
Страница 102: ...Operation manual G9SR Page 76 of 79 My notes...
Страница 105: ...Operation manual G9SR Page 79 of 79 My notes...