Operation manual
G9SR
Page 29 of 79
7.4.4
RESTART LED = Restart
Color: Yellow
ON when Restart input activated.
FLASH when any error occurs.
Fast blinking & ERR fast blinking = Communication error of
another unit
Slow blinking &
ERR slow blinking = Communication error of this unit
See also § 7.5.2
on page 31.
OFF when restart action is not required / not allowed.
7.4.5
EDM LED
= External Device Monitoring
Color: Yellow
ON when EDM function is enabled.
FLASH when any error on External Device Monitoring occurs.
OFF EDM function is disabled.
7.4.6
ON LED
= Outputs
Color: Green
ON when the outputs are ON.
OFF when the outputs are OFF.
7.4.7
OFF/ERR LED = Error
Color: Red
ON when OSSDs are OFF
System startup internal testing failed
FLASH when an error occurs (EDM and Restart leds provide error code).
Fast blinking & RES or COM fast blinki
ng
= Communication error of another unit
Slow blinking & RES or COM slow blinking
= Communication error of this unit
See also § 7.5.2
on page 31.
OFF when all internal diagnostics are successfully passed and OSSDs are ON.