Operation manual
G9SR
Page 11 of 79
Item
Value
Output relay circuit protection
No internal protection
External fuse (5A) required.
Relay life time
Electrical @ maximum allowed load: 100.000
cycles. Mechanical : 10.000.000 cycles.
Unit power supply circuit
protection
External fuses: G9SR-
AD□
-
□ = 1A F
,
G9SR-
EX□
-T90-
□ = 1A F, G9SR
-
BC□
-
□ =
5A F
Input circuit protection
Over voltage protection.
Short circuit creates an error situation.
Incorrect polarity creates an error situation.
Input test pulse duration
1ms
Response timing:
Stand-alone G9SR-
BC□
-
□
Stand-alone G9SR-
AD□
-
□
1 G9SR-
BC□
-
□
&
G9SR-
AD□
-
□
2 G9SR-
BC□
-
□
&
G9SR-
AD□
-
□
G9SR-
AD□
-
□ & 1 G9SR
-
EX□
-
□
-
□
G9SR-
AD□
-
□ & 2 G9SR
-
EX□
-
□
-
□
G9SR-
AD□
-
□ & 3 G9SR
-
EX□
-
□
-
□
1 BC
&
AD & 1 EX
2 BC
&
AD & 1 EX
1 BC
&
AD & 2 EX
2 BC
&
AD & 2 EX
1 BC
&
AD & 3 EX
2 BC
&
AD & 3 EX
< 54ms
< 52ms
< 214ms for system
< 294ms for system
< 58ms
< 61ms
< 64ms
< 218ms
< 298ms
< 222ms
< 302ms
< 225ms
< 306ms
Restart time (OFF
ON)
< 150ms
Insulation resistance
> 20MOhm
Dielectric voltage strength
2500V AC, 50/60 Hz for 1 minute
Operating modes
Automatic/manual restart, EDM, Input Loop
chain and Output Loop chain.
Maximum cabling length
for safety inputs
Maximum length < 100m
and total cable impedance < 250Ohm
Maximum capacitance for BC
model OSSD
330nF
Maximum peak current BC model
OSSD
5A
Cable terminal requirements:
•
3 poles connector:
•
4 poles connector:
•
5 poles connector:
Cable types allowed:
0,2mm
2
to 2.5mm
2
(AWG 24 to AWG 12)
0,2mm
2
to 2.5mm
2
(AWG 24 to AWG 12)
0,2mm
2
to 1,5mm
2
(AWG 24 to AWG 16)
Stranded, Fixed, Ferrules.
Содержание G9SR
Страница 1: ...ZX T Series Cat No J12E EN 03 G9SR Safety Relays OPERATION MANUAL G9SR BC G9SR AD G9SR EX...
Страница 34: ...Operation manual G9SR Page 8 of 79 3 1 Test the OFF behaviour...
Страница 35: ...Operation manual G9SR Page 9 of 79 3 2 Test the ON behaviour...
Страница 102: ...Operation manual G9SR Page 76 of 79 My notes...