![Omron CVM1-CLK21 Скачать руководство пользователя страница 237](http://html1.mh-extra.com/html/omron/cvm1-clk21/cvm1-clk21_operation-manual_742531237.webp)
221
Troubleshooting Using Indicators
Section 9-1
Node Cannot Participate
in Data Link
The following table describes the LNK and M/A indicators when a node can-
not participate in the data links.
Data link participation depends on the Controller Link Unit operating normally
and participating in the Network. Refer to Troubleshooting with RUN, ERC,
ERH and INS Indicators earlier in this section and check Unit operation before
using the following table.
Data Link Cannot be
Stopped
Stopping the data link depends on the Controller Link Unit operating normally
and participating in the Network. Read the above explanations before
attempting to stop operation.
Note Stop the data link from the node at which the LNK indicator is lit (indicating
active data links). Data links cannot be stopped from nodes which do not have
active data links.
Not lit
Not lit
Automatically set data links
are already operating on the
same Network.
Stop the automatically set data
links that are operating and
restart the data links.
There is an error in the startup
node PC.
Refer to the PC’s operation
manual and correct the error. If
the error reoccurs, replace the
PC.
Indicators
Probable cause
Probable remedy
LNK
M/A
Indicators
Probable cause
Probable remedy
LNK
M/A
Lit
---
Data link operating normally.
---
Flashing
Lit
When manual setting is used,
there is an error in the data link
table.
Refer to 5-2-2 Manual Setting
and remake the data link table.
Flashing
Not lit
When automatic setting is
used, the data link parameters
at the startup node are incor-
rect for the local node (the
data link area is out of range
for the local node.)
Refer to 5-2-4 Automatic Set-
ting: “Select All”, reset the
parameters for the startup
node DM Area so that the local
node can participate in the
data link, and then restart the
data link.
When automatic setting is
used, the local node is not set
to participate in the data link at
the startup node.
Stop the data link, reset the
parameters for the startup
node DM Area so that the local
node can participate in the
data link, and then restart the
data link.
Not lit
Lit
When manual setting is used,
there are no data link tables
set for the local node.
Set data link tables for the
local node.
Содержание CVM1-CLK21
Страница 2: ......
Страница 3: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Страница 34: ......
Страница 42: ......
Страница 66: ......
Страница 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Страница 124: ......
Страница 192: ......
Страница 280: ......
Страница 284: ......
Страница 300: ......
Страница 304: ......