249
Status Area and Troubleshooting
Section 9-2
Other Status
Bit status
Probable cause
Probable remedy
Error log exists (IR 19015)
is 1: ON
Error information on the
Controller Link Unit (an
error log) has been
recorded.
Using the Controller Link
Support Software or an
FINS command, read the
cause of the current error.
Alternatively, use past error
log records to troubleshoot
the problem.
Communications controller
send error (IR 19011) is 1:
ON
The Controller Link Unit is
faulty.
Replace the Controller Link
Unit.
Inconsistent network
parameters (IR 19010) is 1:
ON
Indicates that the network
parameters recorded in the
CPU Unit’s EEPROM differ
from the values of the Net-
work in use.
Check the network param-
eters on the Network in
use using the Controller
Link Support Software, and
reset necessary parame-
ters.
Node address duplicate
setting error (IR 19009) is
1: ON
The same node address
has been used more than
once.
Reset so that each node
address is used only once
within the same Network.
EEPROM error (IR 19007)
is 1: ON
An error has occurred
while writing data to the
CPU Unit’s EEPROM.
Check the status of bits
IR 19000 to IR 19002 and
correct any problems
found. If the error occurs
again, replace the CPU
Unit.
PC system setting error (IR
19003) is 1: ON
The EEPROM data is dam-
aged.
Check the status of bits
IR 19000 to IR 19002 and
correct any problems
found. If the error occurs
again, replace the CPU
Unit.
Routing table error
(IR 19002) is 1: ON
The routing table data
within the CPU Unit’s
EEPROM is damaged.
Refer to 7-4 Setting Rout-
ing Tables and reset the
routing tables correctly. If
the error occurs again,
replace the Controller Link
Unit.
There is an error in the
routing table setting.
When using a routing
table, refer to 7-4 Setting
Routing Tabless and reset
the routing tables correctly.
If no routing tables are
being used, delete the
tables.
Data link table error
(IR 19001) is 1: ON
The data link table data in
the EEPROM of the CPU
Unit is damaged.
Refer to 5-3 Starting and
Stopping Data Links and
reset the data link tables
correctly. If the error occurs
again, replace the CPU
Unit.
There is an error in the
data link table settings.
When using manually set
data links, refer to 5-3
Starting and Stopping Data
Links and remake and set
the data link tables cor-
rectly. When manually set
data links are not being
used, delete the data link
tables.
Содержание CVM1-CLK21
Страница 2: ......
Страница 3: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Страница 34: ......
Страница 42: ......
Страница 66: ......
Страница 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Страница 124: ......
Страница 192: ......
Страница 280: ......
Страница 284: ......
Страница 300: ......
Страница 304: ......