255
Error Log
Section 9-3
0117
Hex
Internal buffer full
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Increase number of
retries or reconfig-
ure system to distrib-
ute load.
No
All
0118
Hex
Illegal packet discarded
Check for nodes
sending illegal
packets.
Yes
All
0203
Hex
EEPROM error
01 Hex:
Read error
02: Hex:
Write error
01 Hex:
Data link
tables
02 Hex:
Network
parameters
03 Hex:
Routing
tables
For CVM1 and CV-
series PCs, check
that the PC is not
protected.
Remake and set the
relevant data. If the
error occurs again for
the CVM1 and
CV-series, replace
the CPU Unit and for
the C200HX/HG/HE
PCs, replace the
Controller Link Unit.
Yes
C200HX/HG/
HE, CV,
CQM1H
0206
Hex
Number of participating nodes
decreased (local node still partic-
ipating)
Network
parameters
maximum
node
address
Number of
non-partici-
pating nodes
Check network
parameters, node
participation, cables,
and terminating
resistance.
No
All
0207
Hex
Number of participating nodes
decreased (local node not partic-
ipating)
No
All
0208
Hex
Polling node changed
Address of
previous
polling node
Address of
new polling
node
Check previous
polling node.
No
All
0209
Hex
Inconsistent network parameter
00 Hex
Address of
polling node
Using the Controller
Link Support Soft-
ware, check network
parameters.
Yes
All
020C
Hex
Time out with token
00 Hex
Error status
(see note)
Check network
parameters, node
participation, cables,
and terminating
resistance.
No
All
0210
Hex
Communications controller send
error
00 Hex
Error status
(see note)
Replace the Control-
ler Link Unit.
Yes
All
0211
Hex
Duplicate address error
00 Hex
Local node
address
Reset so that each
node address is used
only once within the
same Network.
No
All
0214
Hex
Node address setting error
Not specified
Check the node
address settings and
correct them.
Yes
CS/CJ,
CQM1H
Error
code
Contents
Detail code
Correction
Written to
EEPROM
Applicable
PC
1st byte
2nd byte
Содержание CVM1-CLK21
Страница 2: ......
Страница 3: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Страница 34: ......
Страница 42: ......
Страница 66: ......
Страница 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Страница 124: ......
Страница 192: ......
Страница 280: ......
Страница 284: ......
Страница 300: ......
Страница 304: ......