15
Basic Procedures
Section 1-4
1-4
Basic Procedures
Preparations
C200HX/HG/HE and CQM1H-series PCs
1,2,3...
1.
Set the node address on the front rotary switches.
• 01 to 32
2.
Set the baud rate and operating level on the front DIP switch.
• 2 M, 1 M, or 500 Kbps
• Operating level 0 or operating level 1 (C200HX/HG/HE PCs only)
3.
Set the terminating resistance on the sliding switch.
• ON or OFF (Only the end nodes are set to ON.)
4.
Register routing tables as required.
CVM1, CV-series, and CS/CJ-series PCs
1,2,3...
1.
Set the Unit number on the front rotary switches.
• 00 to 15 (0 to F: CS/CJ-series display is in hexadecimal)
2.
Set the node address on the front rotary switches.
• 01 to 32
3.
Set the baud rate and operating level on the front DIP switch.
• 2 M, 1 M, or 500 Kbps (wired systems only)
4.
Set the terminating resistance on the front slide switch.
• ON or OFF (Only the terminal node is set to ON.)
5.
Register routing tables.
Data Link Procedure
1,2,3...
1.
Connect power to all nodes.
2.
Connect the Programming Device to the PC.
3.
Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PCs and not necessary for CJ-series PCs unless user-created I/O
tables have been specified).
4.
Set the data link mode in the data link parameters in the DM area of the
startup node to either automatic or manual data link creation using the Pro-
gramming Device.
Manually Setting Data Links
1,2,3...
1.
Register data link tables for all nodes using the Controller Link Support
Software or CX-Programmer.
2.
Start the data links either using the Controller Link Support Software, CX-
Programmer, or by turning ON the Start Bit from the Programming Device.
Automatically Setting Data Links
1,2,3...
1.
Set the DM area of the startup node using the Programming Device.
2.
Start the data links by turning ON the Start Bit from the Programming De-
vice.
Message Service
Procedure
1,2,3...
1.
Turn ON the power.
Содержание CVM1-CLK21
Страница 2: ......
Страница 3: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Страница 34: ......
Страница 42: ......
Страница 66: ......
Страница 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Страница 124: ......
Страница 192: ......
Страница 280: ......
Страница 284: ......
Страница 300: ......
Страница 304: ......