Selecting Communications Instructions
Section 6-2
6-2-2
Message Service Specifications
Item
Specifications
Transmission format
C200HX/HG/HE PCs
1:1 SEND or RECV
1:N SEND (broadcast)
CS/CJ-series, CVM1,CV-series, or CQM1H-series PCs
1:1 SEND, RECV, or CMND
1:N SEND or CMND; (broadcast)
Packet length
SEND: 990 words (1,980 bytes) max.
RECV: 990 words (1,980 bytes) max.
CMND: 1,990 bytes max.
Data content
SEND: Command and response for a request to send data
are transferred.
RECV: Command and response for a request to receive
data are transferred.
CMND: A wide range of command/response data can be
sent.
Number of simulta-
neous commands
C200HX/HG/HE PCs:
One at a time for each of 2 operating level.
CS/CJ-series, CVM1, and CV-series PCs:
One for each of eight ports (ports 0 to 7).
CQM1H-series
One
Response monitor time C200HX/HG/HE or CQM1H-series PCs
00:
Default setting
2 seconds (2 Mbps)
4 seconds (1 Mbps)
8 seconds (500 Kbps)
FF: No
monitoring
01 to FE:
User settings (in increments of 100 ms,
100 to 25,400 ms)
CS/CJ-series, CVM1, and CV-series PCs
0000:
Default setting (2 s)
0001 to FFFF:
User settings (in increments of 0.1 s,
0.1 to6553.5 s)
Number of retries
0 to F:
0 to 15
Содержание CVM1-CLK21
Страница 2: ......
Страница 3: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Страница 34: ......
Страница 42: ......
Страница 66: ......
Страница 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Страница 124: ......
Страница 192: ......
Страница 280: ......
Страница 284: ......
Страница 300: ......
Страница 304: ......