Setting Data Links
Section 5-2
2.
A data link mode can be set in a data link startup node only. The data link
mode setting is determined by the data link mode of the startup node even
if the data link mode settings of the nodes participating in the data links are
different from the settings in the startup node.
3.
In manual setting, a data link table must be set in the data link startup node
and in automatic setting, automatic data link setting parameters must be
set in the data link startup node. Data links will not be started unless the
settings are correct.
5-2-2
Manual Setting
Transfer the data link tables that were created on the Controller Link Support
Software or CX-Net (in CX-Programmer) to the Controller Link Unit or the
Controller Link Support Board (for IBM PC/AT or compatible computers).
The data link tables are transferred from a computer running the Controller
Link Support Software. The computer can either be a node in the network or a
computer attached as a Programming Device.
Transferring from a Programming Device
Note
1.
When transferring data link tables to a CS/CJ-series PC, turn OFF pin 1 of
the DIP switch on the CPU Unit. Otherwise, data link tables cannot be writ-
ten normally.
2.
When transferring the data link tables to a CVM1 or CV-series PC, set the
System Protect Keyswitch on the CPU Unit to “NORMAL.” Otherwise, data
link tables cannot be written normally.
3.
Use the CX-Net in CX-Programmer version 1.20 or later for CQM1H Con-
troller Link Units. The Controller Link Support Software can also be used.
(The Controller Link Support Software can be integrated into the SYSMAC
Support Software. Refer to the Controller Link Support Software Operation
Manual (W308) for details.)
4.
When using the Controller Link Support Software to set a CJ-series Con-
troller Link Unit, use one of the following methods to set the type of PC.
• Set the type of PC to “Others.”
• Add the following information to the device information setting file
(CLKTYPE.TXT) in the Controller Link Support Software to add the
CJ-series PC and then set the CJ-series PC.
CJ1G-CPU44: Same settings as the CS1G-CPU44-E
CJ1G-CPU45: Same settings as the CS1G-CPU45-E
…
Nodes
Controller
Link Unit
CPU Unit
+
Transmissions
Setting data link tables
RS-232C
IBM PC/AT or
compatible
Controller Link
Support Soft
ware or CX-
Net (in CX-
Programmer)
Содержание CVM1-CLK21
Страница 2: ......
Страница 3: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Страница 34: ......
Страница 42: ......
Страница 66: ......
Страница 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Страница 124: ......
Страница 192: ......
Страница 280: ......
Страница 284: ......
Страница 300: ......
Страница 304: ......