47
Component Names and Functions
Section 3-1
Meanings of LED
Indicators
Note Even when the local node does not participate in the data link, the
indicator will be lit if there are manually set data links active on the
network.
For details refer to 10-1 Troubleshooting Using Indicators.
Note The INS, SD, RD, M/A, LNK, and RING LED indicators on Controller Link
Units in standby mode are not lit.
Name
Color
Status
Meaning
RUN
(operating)
Green
Lit
Unit operating normally or, if Communica-
tions Units are used in duplex operation, Unit
operating normally in active mode.
Flashing
If Communications Units are used in duplex
operation, Unit operating normally in standby
mode.
Not lit
Unit error.
P/S
(power supply)
Green
Lit
Backup power is being supplied.
Not lit
Backup power is not being supplied.
ERC (communica-
tions error)
Red
Lit
Communications error, node address setting
error, hardware error or a connection error
between the Optical Controller Link Unit and
SYSMAC LINK.
Not lit
Normal operation
ERH
(PLC error)
Red
Lit
PLC error, PLC interface error, EEPROM
error, unit number error, I/O table not set,
duplex communications setting error, or
duplex settings incomplete
Not lit
No error.
INS
(network participa-
tion)
Yellow
Lit
Unit is participating (inserted) in the network.
Not lit
Unit is not participating (inserted) in the net-
work.
SD
(send)
Yellow
Lit
Data transmission.
Not lit
No data transmission.
RD
(receive)
Yellow
Lit
Data reception.
Not lit
No data reception.
M/A
(data link mode)
Yellow
Data
links
active in
the net-
work.
Data links not active in the net-
work.
Lit
Manual
(See
note.)
Note:
M/A is always not lit when data
links are not active in the network.
Not lit
Auto-
matic
LNK
(data link)
Yellow
Lit
Data links participating.
Flashing
Error in data link table.
Not lit
Not in a data link or data link inactive.
RING
(transmission path
format)
Yellow
Lit
Token-ring mode setting (cable normal)
Flashing
Token-ring mode setting (cable discon-
nected)
Not lit
Token-bus mode setting
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...