36
Message Service Procedure
Section 2-2
8.
Start the data links.
Note Data link Start/Stop Bit (N= unit number):
CS Series: Word 0 of D 100
×
N
CVM1/CV Series: Word 0 of DM 2000 + 100
×
N
9.
Stop the data links.
Note a) Data link Start/Stop Bit (N= unit number):
CS Series: Word 0 of D 100
×
N
CVM1/CV Series: Word 0 of DM 2000 + 100
×
N
b) The data links will not start if there is an error in the data link tables
in the startup node. Data links can be started and stopped using
the Controller Link Support Software.
2-2
Message Service Procedure
The following steps outline the basic procedure for using the message ser-
vice.
1,2,3...
1.
Install and wire the Units.
2.
Prepare for communications.
3.
Turn ON the power to the PLC.
4.
Connect the Programming Device.
Contents
Method
Nodes
Page
Start the data links.
Switch the Data link
Start/Stop Bit (listed
below) from OFF to ON
using either the Program-
ming Device, or the user
program.
Data link startup node
(The Start Bit can be
turned ON in more then
one node to make sure
the data links start even
when the startup node is
down.)
Contents
Method
Nodes
Page
Stop the data links.
Switch the Data link Start/
Stop Bit (listed below)
from OFF to ON using
either the Programming
Device, or the user pro-
gram.
Any node that is active in
the data link
Contents
Remarks
Page
• Mount the Units to the PLCs.
---
• Wire the Network.
---
Contents
Remarks
Page
• Set the unit number.
---
• Set the node address.
---
Contents
Remarks
Page
Turn ON the power to the PLC.
---
---
Contents
Remarks
Page
Connect the Programming Device.
Note
A Programming Console can
be used if there is no duplex
operation.
---
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...