149
Response Codes
Section 6-6
23: No Unit
01
A file device does not exist where spec-
ified.
Mount the Memory Card or disk
02
The specified memory does not exist.
Check the specifications of the installed file
memory.
03
No clock exists.
Check the model number.
24: Start/stop not possi-
ble
01
The data link tables either have not
been created or are incorrect.
Set the data link tables correctly.
25: Unit error
02
Parity/checksum error occurred
because of incorrect data.
Transfer correct data into memory.
03
I/O setting error (The registered I/O
configuration differs from the actual.)
Either change the actual configuration to
match the registered one, or generate the
I/O table again.
04
Too many I/O points
Redesign the system to remain within per-
missible limits.
05
CPU bus error (An error occurred dur-
ing data transfer between the CPU Unit
and a CPU Bus Unit.)
Check the Unit, Service Boards, and cable
connections and issue the ERROR CLEAR
command.
06
I/O duplication error (A rack number,
unit number, or I/O word allocation has
been duplicated.)
Check the system’s settings and eliminate
any settings that occur twice.
07
I/O bus error (An error occurred during
data transfer between the CPU Unit
and an I/O Unit.)
Check the Unit, Service Boards, and cable
connections and issue the ERROR CLEAR
command.
09
SYSMAC BUS/2 error (An error
occurred during SYSMAC BUS/2 data
transfer.)
Check the Unit, Service Boards, and cable
connections and issue the ERROR CLEAR
command.
0A
Special I/O Unit error (An error
occurred during CPU Bus Unit data
transfer.)
Check the Unit, Service Boards, and cable
connections and issue the ERROR CLEAR
command.
0D
Duplication in SYSMAC BUS word allo-
cation.
Check and regenerate the I/O table.
0F
A memory error has occurred in inter-
nal memory, in the Memory Card, or in
Expansion DM during the error check.
If the error occurred in internal memory or
the EM Unit, correct the data in the com-
mand an execute it again.
If the error occurred in a Memory Card or
EM used for file memory, the file data has
been corrupted. Execute the MEMORY
CARD FORMAT command for the PLC.
If the above remedies do not eliminate the
error, replace the faulty memory.
10
Terminator not connected in SYSMAC
BUS System.
Connect the terminator correctly.
Main code
Sub-
code
Probable cause
Remedy
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...