229
Error Log
Section 10-3
0109
Hex
Transmission failed; destination
busy
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Increase number of
retries or reconfig-
ure system to distrib-
ute load.
No
CV, CS
010A
Hex
Transmission failed; communica-
tions controller error
Conduct an echo-
back test and if the
effects of noise are
considerable, recon-
sider the operating
environment. Restart
the Controller Link
Unit. If the error
occurs again,
replace the Unit.
Yes
CV, CS
010B
Hex
Transmission failed; PLC error
Refer to the PLC
operating manual. If
the error occurs
again, replace the
PLC.
No
CV, CS
010C
Hex
Transmission failed; unit number
incorrect
Check unit number
settings to be sure
they are within range
and unique.
No
CV, CS
010D
Hex
Transmission failed; destination
address incorrect
Refer to 7-4 Setting
Routing Tables, and
set a destination
address in the rout-
ing table.
No
CV, CS
010E
Hex
Transmission failed; routing
tables not registered
Refer to 7-4 Setting
Routing Tables, and
set a routing table for
the source node,
destination node,
and relay node.
No
CV, CS
010F
Hex
Transmission failed; routing table
error
Refer to 7-4 Setting
Routing Tables, and
correctly set the rout-
ing table.
No
CV, CS
0110
Hex
Transmission failed; too many
relay points
Check routing tables
and system configu-
ration. Do not try to
access Networks
separated by more
than one other Net-
work.
No
CV, CS
0111
Hex
Transmission failed; command
packet too long
Be sure to use the
FINS command for-
mat.
No
CV, CS
0112
Hex
Transmission failed; header
error.
Be sure to use the
correct FINS com-
mand format.
No
CV, CS
0113
Hex
Transmission failed; I/O setting
error
Check I/O table
accuracy.
No
CV, CS
0114
Hex
Transmission failed; CPU bus
error
Check Unit and cable
connections and
clear error.
No
CV, CS
0115
Hex
Transmission failed; redundant
I/O allocations
Check unit numbers
for redundancy
within the same PLC.
No
CV, CS
Error
code
Contents
Detail code
Correction
Written to
EEPROM
Applicable
PLC
1st byte
2nd byte
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...