Handling and Using GI Cable
Appendix D
The Optical Fiber Cable’s characteristics will deteriorate if the cable remains under tension for a long period, so
be sure to release the tension after installing the cable.
Pull Box and Figure-8 Loops
Bending Radius
The minimum bending radius for Optical Fiber Cable is generally about 10 times the cable’s diameter. Bending
the cable in a smaller radius can increase its transmission loss or break the fiber completely. Bends in the con-
duit must be at least 20 times the cable’s diameter due to the tension member’s characteristics.
When reusing existing conduit, take steps such as installing pull boxes at sharp turns to avoid damaging the
cables.
Splicing Optical Fiber Cables
There are two methods that can be used to splice Optical Fiber Cables.
Fused Connection
With this method, the ends of the fibers are brought together and fused by applying heat from an electrical arc
or other source. This method can provide a low-loss and stable connection; it can be used in a variety of appli-
cations including spicing cables and attaching a cable to a connector with an attached cord.
Special equipment and skills are required for this technique, so this project must be contracted to an Optical
Fiber Cable manufacturer or company specializing in fiber-optic cable repairs.
Example
Connector Connection
If a connector is attached to the optical fiber, the fiber can be connected easily with a connector adapter.
Example
This connection is easy to connect and disconnect, but it can have a relatively high transmission loss so there
must be excess capacity in the system.
"Messenger" line
Pulling end
Pull box
Electrical conduit
Figure-8 loops
Optical Fiber Cable
Electrode
Optical fiber
V groove
Capillary
Plug
Ferrule
Adapter
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...