CS-series Optical Bus Controller Link Units
Appendix C
Communications Specifications
Optical Ring System
Note 1.
The maximum distance between nodes depends on the connector and cable processing methods.
2.
The CS-series PLCs do not have an LR area, but CIO 1000 through CIO 1199 are used automatically
in place of LR 000 to LR 199.
Items
Specifications
Communications method
N:N token bus
Code Manchester
code
Modulation Baseband
code
Synchronization
Flag synchronization (conforms to HDLC frames)
Transmission path form
Daisy-chain
Baud rate
2 Mbps
Maximum transmission dis-
tance
20 km
Maximum distance
between nodes
Crimp cut: 800 m
Adhesive: 1 km (See note 1.)
Media
H-PCF cable (optical two-core cable)
Node connection method
Connected via a special (full-lock connector) connector. (A half-lock connector can also be
used.)
Maximum number of nodes 32 nodes
Communications functions
Data links and message service
Number of data link words
Transmission area per node:
1,000 words (2,000 bytes) max.
Data link area in one PLC (CS-series PLC) (send/receive):
12,000 words (24,000 bytes) max.
Number of data link words in one network (total transmission):
32,000 words (64,000 bytes) max.
Data link areas
Bit areas (IR, AR, LR (See note 2.), CIO), data memory (DM), and extended data memory
(EM)
Message length
2,012 bytes max. (including the header)
RAS functions
Polling node backup function
Self-diagnosis function (hardware checking at startup)
Echoback test and broadcast test (using the FINS command)
Watchdog timer
Error log function
Node bias function
Error control
Manchester code check
CRC check (CCITT X
16
+ X
12
+ X
5
+ 1)
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...