113
Introduction
Section 6-1
CVM1 and CV-series PLCs
SEND
SEND transmits “n” words beginning with S (the beginning word for data
transmission at the local node) to “n” words beginning with D (the beginning
word for data reception at the remote node, N.)
Note
1.
When using CVM1 and CV-series PLCs manufactured prior to April 1996,
the local network address cannot be set to “00.” Set a number other than
“00” as the local network address in the routing tables, and then specify
that number.
2.
With the message service, there is no guarantee that a message to a re-
mote node will reach its destination. It is always possible that the message
may be lost in transit due to noise or some other condition. When using the
message service, it is advisable to prevent this situation from occurring by
performing resend processing at the node where instructions are issued.
With the SEND, RECV, and CMND instructions, resend processing is per-
formed automatically once the number of retries has been set, so be sure
to specify a number other than “0” for the number of retries.
S: Local node beginning send word
D: Remote node beginning receive word
C: Local node beginning control data word
Remote (destination) node N
00 to 3E (Hex): 0 to 62 (*1)
The same data can be broadcast to all nodes
on the network by setting the remote node address to FF
(Hex).
The range of node addresses will vary for networks
other than Controller Link Networks.
(
↑
)SEND(192)
S
D
C
C+1
0
0
C+3
0
0
Number of retries
0 to F (Hex): 0 to 15 retries
Communication port No.
0 to 7 (Hex)
0: Response required
1: Response not required
C+4
C
"n" number of send words
0000 to 03DE (Hex): 1 to 990 words
15
11
8 7
0
Remote (destination) network address
00 (Hex): Local network
01 to 7F (Hex): 1 to 127
C+2
15
11
8 7
0
Remote unit address
00 (Hex):
PLC's CPU Unit
01 (Hex):
Computer (user program)
10 to 1F (Hex): Unit nos. 0 to 15
FE (Hex):
Unit connected to network
15
11 8 7
3
0
Response monitor time
0000 (Hex): 2 s
0001 to FFFF (Hex): 0.1 to 6,553.5 s
(Unit: 0.1 s)
If the transmission speed is slow, then setting
a small value may generate an error. The
standard is approximately 4 seconds at
1 Mbps or 8 seconds at 500 Kbps.
Remote (destination) node N
"n" number
of send
words
n
S
15
0
n
D
15
0
Local node
*1 Only node addresses 1 to 32 can be specified when Optical Bus Controller Link Units/Boards (CLK11)
are combined in a network with Optical Ring Controller Link Units/Boards operating in token-bus mode.
• • •
• • •
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...