240
Locating and Correcting Cable Disconnections
Section 10-4
10-4-4 Clearing the Ring Status Words
When a disconnection has been detected, the disconnected node information
in the ring status words is retained even if the disconnection has been cor-
rected. The data is retained to provide a record of the disconnection if the
connection is just unstable and has been restored automatically. (The discon-
nected node information will be overwritten if another error is detected later.)
The ring status information is recorded independently in each node, so one of
the following methods must be used to clear the ring status words.
• Clear the ring status words with the support software (Controller Link
Support Software Ver. 2.00 or higher.) The support software operation
clears the ring status information in all of the nodes.
• Send the NETWORK DISCONNECT DATA CLEAR command (FINS com-
mand 06 06) from the ladder program or other source. The command
must be sent to all of the nodes.
Note If the power supplies (including backup power supplies) to the nodes are not
turned ON simultaneously, the temporary disconnection will be detected as
the network starts up. When the network is started in token-ring mode, verify
that the disconnection has been corrected automatically by checking the ring
status words or the status of the RING LED indicators and then clear the ring
status words.
The following example shows how to clear the ring status words by sending
FINS command 06 06 from the ladder program. In this example, the Controller
Link Unit’s unit number is 0 and no other Communications Units are mounted
in the local node.
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...