313
Analog Input Terminals
Section 5-7
Terminal Block
Install the following M3 crimp terminals on the signal wires and connect them
to the terminal block.
Note
Tighten the terminal block screws to the specified tightening torque of
0.5 N
⋅
m.
The following diagram shows the terminal block for the SRT2-AD04.
Note
For current input, short terminals V+ and I+.
Wiring
Wire the connector terminals of the Analog Input Terminal as shown below
according to voltage input or current input.
For current input, short terminals V+ and I+. Use the short circuiting fitting
provided to accomplish this.
Input Range and
Conversion Data
The analog data that is input will be converted to digital values according to
the input range.
Note
If the input range is surpassed, the AD conversion data will be fixed at the
upper or lower limit.
–10 to 10 V
Voltages between
–
10 V and 10 V correspond to F448 to 0BB8 Hex (–3000 to
3000). The range of data that can be converted is F31C to 0CE4 Hex (–3300
to 3300). When voltage is negative, it is expressed as 2
’
s complement (16
6.0mm max.
6.0mm max.
AG
NC
AG
NC
NC
NC
BD
H
BS
+
BD
L
BS
–
V0+
I0+
V1+
I1+
V2+
I2+
V3+
I3+
0–
1–
2–
3–
Voltage Input
Current Input
CompoBus/S
communications
CompoBus/S
communications
power supply
(including internal
circuit power supply)
(For current input, short
terminals V+ and I+.)
BS
+
AG
V+
I+
BS
–
AG
+
–
0 V
0 V
V+
I+
–
–
BD
H
BD
L
BD H
BD L