113
CJ1W-SRM21 Master Unit for CJ-series PLCs
Section 4-3
2.
After installing the crimp terminal to the stripped end of the signal wires,
apply vinyl tape or heat-shrinking tube.
Note
Always use the specified crimping tool to install crimp terminals. When a
crimping tool is not used, the terminal cannot be correctly crimped and may
cause the cables to be disconnected.
3.
Check the direction of the connector and insert each of the signal wires se-
curely into the back of the connector holes.
Note
Before inserting the signal wires, check that the connector’s lock screws are
sufficiently loose. If the screws are not loose when the signal wires are
inserted, the signal wires will enter the gap at the back of the connector rather
than the side to be tightened and may not be secured.
4.
Tighten the signal wires securely using the connector’s signal wire lock
screws. A standard screwdriver that is only slim at the end cannot be in-
serted into the back of the screw hole, so use a small flat-blade screwdriver
that is of uniform thickness. The tightening torque is 0.22 to 0.25 N
⋅
m.
Note
Use a precision flat-blade screwdriver and M2 size terminal screws for the
communications connector.
Apply vinyl tape or heat-
shrinking tube
+
(BS
+)
–
(BS
–)
High (BD H)
Low (BD L)
CompoBus/S communications
power supply (supplying
Slaves)
CompoBus/S
communications
data
Communications cable
Communications power supply
(connected to Power Supply Unit.)
+
(BS
+)
–
(BS
–)
Small flat-blade
screwdriver of
uniform thickness