91
CS1W-SRM21 Master Unit for CS-series PLCs
Section 4-2
Set pin 1 (NODE) of the DIP switch as shown in the following table.
Note
1.
The usable node number setting determines the total number of words al-
located, and combined with the DIP switch pin 2 setting, determines the
Slaves’ communication cycle. Refer to
for details.
2.
When the usable node number setting is set to IN0 to IN15 and OUT0 to
OUT15, the CompoBus/S Master Unit is allocated twice as many words in
the PLC’s Special I/O Unit Area (the words for unit number set on the Mas-
ter and the next unit number). The Master’s unit number and the next unit
number cannot be used by another Special I/O Unit mounted to the PLC.
Set pin 2 (DR) of the DIP switch as shown in the following table.
Note
1.
The communications mode of the Master Unit must match that of all
Slaves. If the CompoBus/S System contains a Slave whose communica-
tions mode does not agree with that of the Master Unit, the COMM indica-
tor on that Slave will not light, and normal communications with that Slave
will not be possible. Other Slaves will not be adversely affected. (In such
cases, the COMM indicator on the Master Unit will light normally.) For in-
formation on the Master Unit indicator statuses, refer to
erations of CS-series and CJ-series Master Units
2.
The setting of pin 2 determines the communications distance, baud rate,
and cycle time as shown in the above table.
Set pin 3 of the DIP switch as shown in the following table.
If communications stop mode is set, communications automatically stop when
a remote I/O communications error occurs, thereby preventing system mal-
functions.
Pin 1 setting
Usable node number
setting
Maximum
I/O points
Words allocated in the
Special I/O Unit Area
OFF
IN0 to IN7 and OUT0 to
OUT7 (up to 16 nodes
can be connected)
128 points
(64 inputs,
64 outputs)
10 words (words for one
unit)
Input/output data: 4 input
words and 4 output words
Status information: 2
words
ON
IN0 to IN15 and OUT0 to
OUT15 (up to 32 nodes
can be connected)
256 points
(128 inputs,
128 out-
puts)
20 words (words for two
units)
Input/output data: 8 input
words and 8 output words
Status information: 4
words
Pin 2
setting
Communications
mode setting
Communications
distance
Communications
baud rate
Communications
cycle time
OFF
High-speed Com-
munications Mode
100 m max.
750 kbps
0.5 ms (pin 1 OFF)
or
0.8 ms (pin 1 ON)
ON
Long-distance
Communications
Mode
500 m max.
93.75 kbps
4.0 ms (pin 1 OFF)
or
6.0 ms (pin 1 ON)
Pin 3 setting
Communications stop mode setting
OFF
Communications mode
Continues remote I/O communications when a communica-
tions error occurs.
ON
Communications stop mode
Stops remote I/O communications when a communications
error occurs.