322
Analog Output Terminals
Section 5-8
SW102
Note
Output range is set separately for Output 0 and Output 1. An example is
shown below.
Output 0: 4 to 20 mA (Pins 1, 2, 3 = OFF, OFF, ON)
Output 1: 1 to 5 V (Pins 4, 5, 6 = ON, OFF, OFF)
Internal Circuits
The following diagram shows the internal circuits for the SRT2-DA02.
Terminal Block
Install the following M3 crimp terminals on the signal wires and connect them
to the terminal block.
Note
Tighten the terminal block screws to the specified tightening torque of
0.5 N
⋅
m.
Pin 1
Pin 2
Pin 3
Range setting for Output 0
Pin 4
Pin 5
Pin 6
Range setting for Output 1
OFF
OFF
OFF
0 to 5 V (Factory setting)
ON
OFF
OFF
1 to 5 V
OFF
ON
OFF
0 to 10 V
ON
ON
OFF
–10 to 10 V
OFF
OFF
ON
4 to 20 mA
Do not set to any values but those given above.
Pin 7
Pin 8
Output setting for communications error
OFF
OFF
Clear to lower output limit (Factory setting)
OFF
ON
Clear to upper output limit
ON
OFF
0 V output (When output range is
–
10 to 10 V.)
Clear to lower output limit (Any other time.)
ON
ON
Hold output
Output range setting
Output setting for communications error
V +
–
I +
V +
–
I +
BS
BS
BD H
BD L
DC static
converter
(Insulated)
Inter
nal
circuitr
y
Analog GND
Output 0
Output 1
+
–
6.0mm max.
6.0mm max.