216
Connector Terminals
Section 5-2
Models with MIL Connectors
SRT2-VOD16ML/VOD16ML-1
Indicators
The following table shows the meaning of the indicators.
DIP Switch
The DIP switch is located on the base of the Connector Terminal.
Note
Always turn OFF the Slave before changing DIP switch settings.
Communications connector
Used to connect CompoBus/S communications data (BD H, BD L), communications
power supply, and I/O power supply
One compatible connector is provided as standard.
Indicators
Indicate the status of the Slave and communications, and
output status of each contact. (Lit when the output is ON.)
DIP Switch
The DIP switch's pins have the following functions:
Pins 1 to 4: Node number setting
Pins 5 and 6: Reserved (Always OFF.)
Pin 7: Communications mode setting
Pin 8: Hold/Clear outputs for communications error
View from (A) (base)
DIN Track Mounting Hook
Output Connector (MIL Connector)
Connect 16 outputs with MIL connector
XG4M-2030-T MIL Connector and compatible cable are sold separately.
Indicator
Status
Meaning
PWR (green)
ON
The communications power supply is ON.
OFF
The communications power supply is OFF.
COMM (yellow)
ON
Normal communications
OFF
A communications error has occurred or the Unit is
in standby status.
ERR (red)
ON
A communications error has occurred.
OFF
Normal communications or the Unit is in standby sta-
tus.
0 to 7 (8 outputs)
0 to 15 (16 outputs)
ON
The corresponding output is ON.
OFF
The corresponding output is OFF or the Unit is in
standby status.
Hold/Clear outputs for communications error
Communications mode setting
Reserved (Always OFF.)
Node number setting