314
Analog Input Terminals
Section 5-7
bits). In the event of disconnection, the data becomes the same value as in
the case of 0 V input (0000 Hex).
0 to 10 V
Voltages between 0 V and 10 V correspond to 0000 to 1770 Hex (0 to 6000).
The range of data that can be converted is FED4 to 189C Hex (–300 to 6300).
When voltage is negative, it is expressed by 2
’
s complement (16 bits). In the
event of disconnection, the data becomes the same value as in the case of
0 V input (0000 Hex).
0 to 5 V
Voltages between 0 V and 5 V correspond to 0000 to 1770 Hex (0 to 6000).
The range of data that can be converted is FED4 to 189C Hex (–300 to 6300).
When voltage is negative, it is expressed by 2
’
s complement (16 bits). In the
event of disconnection, the data becomes the same value as in the case of
0 V input (0000 Hex).
1 to 5 V
Voltages between 1 V and 5 V correspond to 0000 to 1770 Hex (0 to 6000).
The range of data that can be converted is FED4 to 189C Hex (–300 to 6300).
Hexadecimal (decimal)
conversion data
Voltage
0CE4 (3300)
0BB8 (3000)
F448 (–3000)
F31C (–3300)
0000 (0)
0 V
–11 V –10 V
10 V 11 V
Hexadecimal (decimal)
conversion data
Voltage
189C (6300)
1770 (6000)
0000 (0)
0 V
FED4 (–300)
–0.5 V
10 V 10.5 V
Hexadecimal (decimal)
conversion data
Voltage
189C (6300)
1770 (6000)
0000 (0)
0 V
FED4 (–300)
–0.25 V
5 V 5.25 V