CQM1-SRM21-V1 Master Unit for CQM1 PLCs
Section 4-4
An Analog Terminal uses 64, 48, 32, or 16 points. For this reason, in 8-point
mode, I/O allocations are as shown in the following table.
If a node number is outside the setting range, the words allocated to the Slave
will extend beyond the input or output area, which will prevent the Slave par-
ticipating in communications. If this happens, the COMM indicator will not
light.
Connector Terminals with 32 inputs or 32 outputs are allocated the words for
four 8-point nodes, i.e., they are allocated two I/O words. Therefore, the fol-
lowing nodes will be used in addition to the set nodes. Connector Terminals
with 16 inputs or 16 outputs will be allocated I/O as Slaves with 16 inputs or
Slaves with 16 outputs for the node number setting.
If a node number is not within the setting range, the words allocated to the
Slave will extend beyond the input or output area, which will prevent the Slave
from participating in communications. If this happens, the COMM indicator will
not light.
Number of points
allocated
Node number
setting
Node numbers used
Valid setting range
2 words
allocated
4 words
allocated
8 words
allocated
64 points
SRT2-AD04: 4 inputs
Odd number
Node number setting
−
1 to node
number s 6
Not possi-
ble
Not possi-
ble
0 to 1
Even number
Node number setting to node num-
ber s 7
48 points
SRT2-AD04: 3 inputs
Odd number
Node number setting
−
1 to node
number s 4
Not possi-
ble
Not possi-
ble
0 to 3
Even number
Node number setting to node num-
ber s 5
32 points
SRT2-AD04: 2 inputs
SRT2-DA02: 2 outputs
Odd number
Node number setting
−
1 to node
number s 2
Not possi-
ble
0 to 1
0 to 5
Even number
Node number setting to node num-
ber s 3
16 points
SRT2-AD04: 1-input
SRT2-DA02: 1-output
Odd number
Node number setting
−
1 to node
number setting
0 to 1
0 to 3
0 to 7
Even number
Node number setting to node num-
ber s 1
Node number set-
ting
Node numbers used
Valid setting range
2 words
allocated
4 words
allocated
8 words
allocated
Odd number
Node number setting
– 1 to node number
s 2
Not possi-
ble
0 to 1
0 to 5
Even number
Node number setting
to node number set-
ting + 3