347
Sensor Amplifier Terminals
Section 5-11
4
Press the teaching button for three seconds minimum with or
without a sensing object. In the case of the E3X-NM, select a
channel with the channel selector, at which time the stability
indicator for the selected channel will flash.
The teaching indicator (red) turns green.
The built-in buzzer beeps once when the color of the teaching
indicator is red.
The built-in buzzer beeps continuously when the color of the
teaching indicator is green.
Note:
The built-in buzzer will stop beeping when the teaching
button is no longer being pressed.
5
Set the mode selector to RUN to complete the sensitivity set-
ting.
The teaching indicator is OFF.
Note:
When the sensitivity is set to maximum, the sensitivity
will be automatically adjusted regardless of the set dis-
tances of the fibers or light.
6
Select the logical output required with the operation mode
selector.
Procedure
Operation
E3X-NT
E3X-NM
TEACH
TEACH
TEACH
RUN
TEACH
TIMER
SET
RUN
L
D
ON
ON
1
2
3
4
L ON
D ON
CH