331
I/O Link Units for CPM2C
Section 5-10
Allocation to Master CPU
Unit
The 8 input and 8 output points allocated to the I/O memory of the CPM1A or
CPM2A CPU Unit are allocated to the Special I/O Unit data area of the Master
CPU Unit according to the node number.
Both 8 input and 8 output points use the same node number.
For example, if the range of node numbers IN0 to IN7 and OUT0 to OUT7 is
set, and node number 0 is used, data will be input from bits 00 to 07 of word n
(Output Slave 0) and data will be output to bits 00 to 07 of word n + 4 (Input
Slave 0).
5-10 I/O Link Units for CPM2C
5-10-1 CPM2C-SRT21 I/O Link Unit for CPM2C
Specifications
The following table shows the ratings and I/O specifications for the CPM2C-
SRT21.
Ratings
Note
CompoBus/S communications power supply is not connected.
Standard Specifications
Conform to standard CPM2C specifications.
Master PLC (CS Series)
Node number is 0
CPU Unit
Because node
number is 0*
I/O Memory
Output
IR 2000
(n)
Input
IR 2004
(n+4)
8 points
CompoBus/S
Master Unit
No. 0
Output Slave 0
I/O Link Unit for
CPM1A/CPM2A
30-point I/O CPU Unit
I/O Memory
8 points
8 points
Input
IR 002
Output
IR 012
*: For node numbers IN0 to IN7/OUT0 to OUT7
CompoBus/S
Network
Input Slave 0
8 points
Item
Specification
Model
CPM2C-SRT21
I/O points
8 input points, 8 output points
(All the I/O points use the same node number. I/O is per-
formed only with I/O memory of CPM2C, not with external
devices. One input word and output word of CPM2C are
allocated.)
Connection to CPM2C
Connect expansion I/O connecting cable to the expansion
connector of the CPU Unit or the Expansion Unit.
(Up to 5 Units are connectable.)
Power supply type
---
Communications power
supply and internal cir-
cuits power supply
Supplied from CPM2C CPU Unit. (See note.)
Node number settings
The node number is set on a DIP switch. (Set the node
number before turning ON the CPM2C CPU Unit.)
Weight
Approx. 150 g