164
Remote Terminals
Section 5-1
Note
The current consumption is the value with all 4 and 8 and 16 points turned ON
excluding the current consumption of the external sensor connected to the
input Remote Terminal and the current consumption of the load connected to
the output Remote Terminal.
Output Specifications
Slave Components
The following diagram shows the main components of the SRT2-OD08 Tran-
sistor Remote Terminal. The functions of these components are described
below.
Node number settings
The node number is set on a DIP switch. (Set the node
number before turning ON the Slave.)
Weight
SRT
@
-OD04: 80 g max.
SRT
@
-OD08: 80 g max.
SRT
@
-OD16: 110 g max.
SRT
@
-OD04-1: 80 g max.
SRT
@
-OD08-1: 80 g max.
SRT
@
-OD16-1: 110 g max.
Item
Specification
Item
Specification
Rated output current
0.3 A/point
Residual voltage
0.6 V max.
SRT
@
-OD
@@
: Between each output terminal and G
SRT
@
-OD
@@
-1: Between each output terminal and V
Leakage current
0.1 mA max.
ON delay time
0.5 ms max.
OFF delay time
1.5 ms max.
Insulation method
Photocoupler
Output indicators
LED (yellow)
DIP Switch
Open the cover to reveal the DIP switch. The DIP switch's
pins have the following functions:
Pin 1: Hold/clear outputs for communications error
Pin 2: Communications mode setting (SRT2 Series)
or Reserved (Always OFF) (SRT1 Series)
Pins 3 to 6: Node number setting
Mounting Screw Holes
Used when screwing the Unit to a control panel.
Terminal Block
Connect the CompoBus/S communications cable, communications
power supply, I/O power supply, and output devices such as relays
and indicators to the terminal block.
CompoBus/S Indicators
Indicate the status of the Slave and communications.
Output Indicators
Indicate the status of each contact.
(Lit when the output is ON.)
The SRT
(
-OD04 and SRT
(
-OD04-1 have 4 indicators,
the SRT
(
-OD08 and SRT
(
-OD08-1 have 8 indicators, and
the SRT
(
-OD16 and SRT
(
-OD16-1 have 16 indicators.
DIN Track Mounting Hook
Used when mounting the Unit to a DIN track.