4-168
4-4 Communication Function
4
Functions
The detailed field configuration is shown below. The function code of the exception response is the
value of the query function code to which 80h is added. The exception code shows the cause of
exception response.
Saving the Change to the Holding Register (Enter Command)
Even if using the command to write into the holding register (06h) or into the consecutive holding
registers (10h), no change can be saved in the Inverter's memory element. If the Inverter power
shuts off without saving any changes, the holding register returns to the status before the changes
were made. To save the holding register changes in the Inverter's memory element, the "Enter
Command" must be issued according to the following procedure.
When the control parameters are changed, the motor parameters must be re-calculated. In this
case, perform recalculation with this register.
To issue the Enter command
Write all memory data into the holding register with the write command (06h), and write re-
calculated motor parameters into holding register 0900h. Below are the values to be written into the
holding register.
Note
• The Enter command needs considerable time. Monitor the data writing signal (coil number 001Ah)
to check whether the data is being written.
• Since the Inverter's memory element has a limit on the number of rewrites (approx. 100,000 times),
the Inverter life may be shortened if enter commands are frequently used.
Function code
Exception code
Query
Exception
response
Code
Description
01h
81h
01h
An unsupported function has been specified.
03h
83h
02h
Specified address does not exist.
05h
85h
03h
Specified data has an unacceptable format.
06h
86h
21h
Data is out of the Inverter's range for writing into the holding register.
0Fh
8Fh
22h
The Inverter does not allow this function.
• Has attempted to change the register that cannot be changed
during operation.
• Has issued the enter command during operation (UV).
• Has written into the register during trip (UV).
• Has written into the read-only register (coil).
10h
90h
Set value
Description
0000
Motor parameter recalculation
0001
Set value storage
Other than the above
Motor parameter recalculation and set value storage
Содержание 3G3RX Series
Страница 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Страница 2: ......
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Страница 22: ......
Страница 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Страница 48: ......
Страница 108: ......
Страница 324: ......
Страница 325: ...Chapter 5 Maintenance Operations 5 1 Protective Functions and Troubleshooting 5 1 5 2 Warning Function 5 10 ...
Страница 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Страница 348: ......
Страница 349: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Dimensional Drawing 7 6 7 3 Options 7 14 ...
Страница 358: ...7 9 7 2 Dimensional Drawing 7 Specifications 3G3RX A2300 A4300 368 79 265 310 10 510 540 2 φ10 195 45 80 265 ...
Страница 360: ...7 11 7 2 Dimensional Drawing 7 Specifications 3G3RX A2550 380 670 700 2 φ12 12 380 480 250 352 79 ...
Страница 361: ...7 12 7 2 Dimensional Drawing 7 Specifications 3G3RX A4750 A4900 2 φ12 2 12 300 390 268 700 79 670 357 ...
Страница 362: ...7 13 7 2 Dimensional Drawing 7 Specifications 3G3RX A411K A413K 2 φ12 2 12 380 480 270 740 79 710 480 ...
Страница 369: ...7 20 7 3 Options 7 Specifications 3G3AX RBC4001 3G3AX RBC6001 100 150 280 300 5 70 100 70 150 390 410 5 ...
Страница 392: ......
Страница 393: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 41 Appendix 3 Life Alarm Output App 42 ...
Страница 436: ......
Страница 437: ...Index ...
Страница 441: ......