Functions
PID Output Limit Function
• This function limits PID output within a variable range relative to the target value.
• To use this function, set PID output limit function A078. The output frequency will be limited within
a range of "target value ± (A078)", with the maximum frequency defined as 100%.
• With A078 set to 0.0, this function is disabled.
PID Reverse Output
• When a PID operation result is a negative value under normal PID control, the frequency reference
to the Inverter is limited at 0 Hz. However, if PID selection A071 is set to "02" (reverse output
enabled), reverse output can be provided for the Inverter when the PID operation result is a negative
value.
• When A071 = 02, the above-mentioned PID variable range limit function and the PID output stop
function are disabled.
PID Gain Adjustment
• If a stable response cannot be obtained in PID function operation, adjust each gain as follows
according to the situation.
•Feedback value variation is slow when the target value is changed.
→
Raise P gain A072.
•The feedback value changes fast but isn't stable.
→
Lower P gain A072.
•The target and feedback values wouldn't match smoothly.
→
Lower I gain A073.
•The feedback value fluctuates unstably.
→
Raise I gain A073.
•Response is slow even with P gain raised.
→
Raise D gain A074.
•With P gain raised, the feedback value vibrates and isn't stable.
→
Lower D gain A074.
Excessive Deviation/Output
• You can set PID deviation excessive level C044 during PID control. With this function allocated,
the multi-function output terminal is turned on when the PID deviation
ε
reaches the set level in
C044.
• C044 can be set from 0 to 100. The setting corresponds to the range of 0 to the maximum target
value.
• Allocate 04 (OD) to any of multi-function output terminals C021 to C025 or relay output terminal
C026.
Feedback Comparison Signal
• If a PID feedback value is out of the specified range, it can be output to a multi-function output
terminal.
• Allocate 31 (FBV) to any of multi-function output terminals C021 to C025 or relay output terminal
C026.
PID output (%)
PID target
value
PID output range
PID variable range (A078)
PID variable range (A078)
Time (s)
Содержание 3G3RX Series
Страница 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Страница 2: ......
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Страница 22: ......
Страница 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Страница 48: ......
Страница 108: ......
Страница 324: ......
Страница 325: ...Chapter 5 Maintenance Operations 5 1 Protective Functions and Troubleshooting 5 1 5 2 Warning Function 5 10 ...
Страница 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Страница 348: ......
Страница 349: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Dimensional Drawing 7 6 7 3 Options 7 14 ...
Страница 358: ...7 9 7 2 Dimensional Drawing 7 Specifications 3G3RX A2300 A4300 368 79 265 310 10 510 540 2 φ10 195 45 80 265 ...
Страница 360: ...7 11 7 2 Dimensional Drawing 7 Specifications 3G3RX A2550 380 670 700 2 φ12 12 380 480 250 352 79 ...
Страница 361: ...7 12 7 2 Dimensional Drawing 7 Specifications 3G3RX A4750 A4900 2 φ12 2 12 300 390 268 700 79 670 357 ...
Страница 362: ...7 13 7 2 Dimensional Drawing 7 Specifications 3G3RX A411K A413K 2 φ12 2 12 380 480 270 740 79 710 480 ...
Страница 369: ...7 20 7 3 Options 7 Specifications 3G3AX RBC4001 3G3AX RBC6001 100 150 280 300 5 70 100 70 150 390 410 5 ...
Страница 392: ......
Страница 393: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 41 Appendix 3 Life Alarm Output App 42 ...
Страница 436: ......
Страница 437: ...Index ...
Страница 441: ......