4-86
4-2 Function Mode
4
Functions
(Example 3) If "01" (frequency matching start) is selected in reset frequency matching selection C103, frequency
matching start is also enabled when the power is turned on again. When C103 = 00 (0-Hz start), the
retry wait time (b003) is ignored. Even if "frequency matching start" is selected, however, the
Inverter may start at 0 Hz if:
• The output frequency is equal to or lower than 1/2 of the base frequency
• The motor induction voltage quickly attenuates
Note: The counters used for the Inverter's internal protection are cleared during reset.
To shut off the Inverter's output via a multi-function input terminal, use the free-run stop
terminal (FRS).
(Example 4) Frequency pull-in restart
Note: If a reset signal is input during the retry wait time, the value of "frequency at interruption"
stored in the Inverter is cleared, resulting in a 0-Hz start.
3-wire Input Function
• This function helps start and stop the Inverter using an auto-recovery contact (e.g. pushbutton
switch).
Power
supply
FW
Motor rpm
Free running
Frequency matching
• After the retry wait time (b003) elapses, the
Inverter starts output from the b030 set value.
The Inverter then decelerates according to
the b029 setting, while keeping the output
current at the b028 set value.
• When the frequency matches the voltage, the
Inverter accelerates again, and the frequency
is restored to the original level.
• If an overcurrent trip occurs under this
method, reduce the b028 setting.
Output
current
FW
RS
b028
Decelerates
according to b029.
Frequency selected
in b030
Trip occurs
b003
Motor rpm
Inverter output
frequency
Data
Symbol
Function name
Status
Description
20
STA
3-wire start
ON
Starts with auto recovery contacts.
OFF
Irrelevant to the motor operation.
21
STP
3-wire stop
ON
Stops with auto recovery contacts.
OFF
Irrelevant to the motor operation.
22
F/R
3-wire forward/reverse
ON
Reverse
OFF:
Forward
Содержание 3G3RX Series
Страница 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Страница 2: ......
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Страница 22: ......
Страница 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Страница 48: ......
Страница 108: ......
Страница 324: ......
Страница 325: ...Chapter 5 Maintenance Operations 5 1 Protective Functions and Troubleshooting 5 1 5 2 Warning Function 5 10 ...
Страница 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Страница 348: ......
Страница 349: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Dimensional Drawing 7 6 7 3 Options 7 14 ...
Страница 358: ...7 9 7 2 Dimensional Drawing 7 Specifications 3G3RX A2300 A4300 368 79 265 310 10 510 540 2 φ10 195 45 80 265 ...
Страница 360: ...7 11 7 2 Dimensional Drawing 7 Specifications 3G3RX A2550 380 670 700 2 φ12 12 380 480 250 352 79 ...
Страница 361: ...7 12 7 2 Dimensional Drawing 7 Specifications 3G3RX A4750 A4900 2 φ12 2 12 300 390 268 700 79 670 357 ...
Страница 362: ...7 13 7 2 Dimensional Drawing 7 Specifications 3G3RX A411K A413K 2 φ12 2 12 380 480 270 740 79 710 480 ...
Страница 369: ...7 20 7 3 Options 7 Specifications 3G3AX RBC4001 3G3AX RBC6001 100 150 280 300 5 70 100 70 150 390 410 5 ...
Страница 392: ......
Страница 393: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 41 Appendix 3 Life Alarm Output App 42 ...
Страница 436: ......
Страница 437: ...Index ...
Страница 441: ......