4-117
4-2 Function Mode
4
Func
tions
High-torque Multi-operation
• When "sensorless vector control" or "0-Hz sensorless vector control" is selected with a single
Inverter, this function controls two motors of the same type to drive a single load.
• To use this function, you set the same parameters as when you select "Sensorless Vector Control"
(page 4-113) or "0-Hz Sensorless Vector Control" (page 4-114). However, set the motor
parameters as follows:
• Set motor parameters R1, R2, and L to one half of the set value for one motor.
• Set motor parameter Io to be twice the set value for one motor.
• Set motor parameter J to one half of the total moment of inertia of two motors and loads
connected to these motors.
• Select the motor capacity value closest to the total capacity of two motors.
• When different loads are driven with two motors, a fluctuation in one load affects the operating
condition of the other, which may hinder normal control.
To prevent this, be sure to operate a system in a way that the load driven by two motors is regarded
as one load.
Stabilization Parameter
• This function adjusts to reduce motor hunting.
• In case of motor hunting, check whether motor capacity H003/H203 and motor pole number
selection H004/H204 match your motor. If they do not, match them. If the motor's primary
resistance is smaller than that of the standard motor, increase the H006/H206/H306 set value
gradually. To run a motor with a capacity larger than the Inverter's rated capacity, reduce the set
value.
• Other than this function, the following methods are suggested to reduce hunting:
Lower the carrier frequency (b083). (Refer to page 4-65.)
Lower the output voltage gain (A045). (Refer to page 4-24.)
Related functions
A044/A244, F001, b040, b041 to b044, H002/H202, H003/H203, H004/
H204, H005/H205, H020/H220, H021/H221, H022/H222, H023/H223,
H024/H224, H050/H250, H051/H251, H052/H252
Parameter No.
Function name
Data
Default setting
Unit
H006/H206/H306
Stabilization parameter
0. to 255.:
If hunting occurs, adjust the set value.
100.
⎯
A045
Output voltage gain
20. to 100.:
If hunting occurs, reduce the set value.
100
%
b083
Carrier frequency
0.5 to 15.0:
If hunting occurs, reduce the set value.
5.0
kHz
Содержание 3G3RX Series
Страница 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Страница 2: ......
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Страница 22: ......
Страница 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Страница 48: ......
Страница 108: ......
Страница 324: ......
Страница 325: ...Chapter 5 Maintenance Operations 5 1 Protective Functions and Troubleshooting 5 1 5 2 Warning Function 5 10 ...
Страница 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Страница 348: ......
Страница 349: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Dimensional Drawing 7 6 7 3 Options 7 14 ...
Страница 358: ...7 9 7 2 Dimensional Drawing 7 Specifications 3G3RX A2300 A4300 368 79 265 310 10 510 540 2 φ10 195 45 80 265 ...
Страница 360: ...7 11 7 2 Dimensional Drawing 7 Specifications 3G3RX A2550 380 670 700 2 φ12 12 380 480 250 352 79 ...
Страница 361: ...7 12 7 2 Dimensional Drawing 7 Specifications 3G3RX A4750 A4900 2 φ12 2 12 300 390 268 700 79 670 357 ...
Страница 362: ...7 13 7 2 Dimensional Drawing 7 Specifications 3G3RX A411K A413K 2 φ12 2 12 380 480 270 740 79 710 480 ...
Страница 369: ...7 20 7 3 Options 7 Specifications 3G3AX RBC4001 3G3AX RBC6001 100 150 280 300 5 70 100 70 150 390 410 5 ...
Страница 392: ......
Страница 393: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 41 Appendix 3 Life Alarm Output App 42 ...
Страница 436: ......
Страница 437: ...Index ...
Страница 441: ......