4-3 Functions When Option PG Board (3G3AX-PG01) Is Used
4
Functions
(1) When the RUN command is turned on with the ORT terminal turned on, the Inverter accelerates to the
orientation speed (P015), and then performs constant speed operation.
(If the RUN command is turned on during operation, the operation speed changes to the orientation speed
when the ORT terminal is turned on.)
(2) After the orientation speed is reached, the Inverter shifts to the position control mode when the first Z-pulse
is detected.
(3) During forward run, position control is performed with a target value of "Orientation stop position (P014) + one
rotation"; During reverse run, with a target value of "Orientation stop position (P014) + two rotations".
In this step, the higher the position loop gain (P023), the shorter the deceleration time (regardless of the
deceleration time setting).
(4) After the remaining number of pulses reaches the position ready range setting (P017), the Inverter outputs
the POK signal after the position ready delay time setting (P018) elapses. (The POK output remains until the
ORT signal is turned off.)
After positioning is completed, the servo lock status remains until the RUN command is turned off.
Note 1: Do not set a high frequency for the orientation speed, because positioning must be completed within two
rotations during deceleration. Otherwise, overvoltage protection may cause a trip.
Note 2: Orientation stop position is defined as 4096 (0 to 4095) divisions of one forward rotation from the
reference point. (The number of divisions is fixed to 4096, regardless of the encoder's number of pulses.)
The reference point is defined as the point where the pulse is input between EZP and EZN. Below is the
layout of the stop target position. (Positive-phase connection)
Orientation stop position conceptual drawing
RUN commands (FW/RV)
ORT terminal
Z pulse
Output
frequency
Orientation speed setting (P015)
ON
ON
ON
POK signal
Position ready range setting (P017)
Position ready delay time setting (P018)
Speed control Position control
(1)
(2)
(3)
(4)
Position of Z pulse
Reference point
0
1024
3072
2048
Motor shaft viewed from motor
shaft load side
Содержание 3G3RX Series
Страница 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Страница 2: ......
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Страница 22: ......
Страница 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Страница 48: ......
Страница 108: ......
Страница 324: ......
Страница 325: ...Chapter 5 Maintenance Operations 5 1 Protective Functions and Troubleshooting 5 1 5 2 Warning Function 5 10 ...
Страница 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Страница 348: ......
Страница 349: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Dimensional Drawing 7 6 7 3 Options 7 14 ...
Страница 358: ...7 9 7 2 Dimensional Drawing 7 Specifications 3G3RX A2300 A4300 368 79 265 310 10 510 540 2 φ10 195 45 80 265 ...
Страница 360: ...7 11 7 2 Dimensional Drawing 7 Specifications 3G3RX A2550 380 670 700 2 φ12 12 380 480 250 352 79 ...
Страница 361: ...7 12 7 2 Dimensional Drawing 7 Specifications 3G3RX A4750 A4900 2 φ12 2 12 300 390 268 700 79 670 357 ...
Страница 362: ...7 13 7 2 Dimensional Drawing 7 Specifications 3G3RX A411K A413K 2 φ12 2 12 380 480 270 740 79 710 480 ...
Страница 369: ...7 20 7 3 Options 7 Specifications 3G3AX RBC4001 3G3AX RBC6001 100 150 280 300 5 70 100 70 150 390 410 5 ...
Страница 392: ......
Страница 393: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 41 Appendix 3 Life Alarm Output App 42 ...
Страница 436: ......
Страница 437: ...Index ...
Страница 441: ......