4-61
4-2 Function Mode
4
Func
tions
Momentary Power Interruption Non-stop Deceleration Stop (b050 = 01)
• After the power is shut off during operation, this function decelerates the Inverter to a stop while
keeping the voltage below the momentary power interruption non-stop deceleration level (b052).
• To use this function, remove the J51 connector cable connected between terminals Ro and To,
and connect the cable from main terminal P to Ro, and from N to To. The cable size should be 0.75
mm
2
or larger.
• If the power is shut off during operation and the voltage falls below the momentary power
interruption non-stop function starting voltage (b051), the frequency deceleration width decreases
at the momentary power interruption non-stop deceleration starting width (b054), and then the
Inverter decelerates for the momentary power interruption non-stop deceleration time (b053).
• If an overvoltage condition (momentary power interruption non-stop deceleration level b052 or
higher) occurs because of regeneration during deceleration, the Inverter is kept in the LAD STOP
status until the overvoltage condition is reset.
*1. When the momentary power interruption non-stop deceleration level (b052) < the momentary
power interruption non-stop function starting voltage (b051), the Inverter performs this function
by increasing the momentary power interruption non-stop deceleration level (b052) to the
momentary power interruption non-stop function starting voltage (b051). (The set value will not
be changed.)
If b052 is lower than the incoming voltage or equivalent (DC voltage or equivalent after
rectification [incoming voltage ×
√⎯
2]), the Inverter is brought into the LAD STOP status at power
recovery during execution of this function, disabling deceleration. (The Inverter will accept
neither a STOP command nor frequency reference change until operation is complete.) Make
sure that the b052 setting is higer than the normal incoming voltage or equivalent.
*2. This function is not reset before the operation is complete and stopped. To run the Inverter after
power recovery during this function, input the RUN command following the STOP command
(RUN command OFF) after a stop condition.
*3. If the momentary power interruption non-stop deceleration starting width (b054) is too large, an
overcurrent trip occurs because of rapid deceleration. If b054 is too small, or if the momentary
power interruption non-stop deceleration time (b053) is too long, an undervoltage trip occurs
because of insufficient regeneration power.
Time (s)
Time (s)
b052
b051
b053
b054
Undervoltage
level
Output
frequency (Hz)
Main circuit P-N
voltage
VPN (V)
Содержание 3G3RX Series
Страница 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Страница 2: ......
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Страница 22: ......
Страница 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Страница 48: ......
Страница 108: ......
Страница 324: ......
Страница 325: ...Chapter 5 Maintenance Operations 5 1 Protective Functions and Troubleshooting 5 1 5 2 Warning Function 5 10 ...
Страница 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Страница 348: ......
Страница 349: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Dimensional Drawing 7 6 7 3 Options 7 14 ...
Страница 358: ...7 9 7 2 Dimensional Drawing 7 Specifications 3G3RX A2300 A4300 368 79 265 310 10 510 540 2 φ10 195 45 80 265 ...
Страница 360: ...7 11 7 2 Dimensional Drawing 7 Specifications 3G3RX A2550 380 670 700 2 φ12 12 380 480 250 352 79 ...
Страница 361: ...7 12 7 2 Dimensional Drawing 7 Specifications 3G3RX A4750 A4900 2 φ12 2 12 300 390 268 700 79 670 357 ...
Страница 362: ...7 13 7 2 Dimensional Drawing 7 Specifications 3G3RX A411K A413K 2 φ12 2 12 380 480 270 740 79 710 480 ...
Страница 369: ...7 20 7 3 Options 7 Specifications 3G3AX RBC4001 3G3AX RBC6001 100 150 280 300 5 70 100 70 150 390 410 5 ...
Страница 392: ......
Страница 393: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 41 Appendix 3 Life Alarm Output App 42 ...
Страница 436: ......
Страница 437: ...Index ...
Страница 441: ......