4-114
4-2 Function Mode
4
Functions
Note 1: Make sure that the carrier frequency (b083) is not lower than 2.1 kHz. If the carrier frequency is lower than
2.1 Hz, the Inverter does not operate normally.
Note 2: To use lower rank motor size than the Inverter, set a torque limit value (b041 to b044), while keeping the
value
α
, calculated with the following formula, at 200% or lower. Otherwise, the motor may burn out.
α
= Torque limit set value × (Inverter capacity) / (Motor capacity)
(Example) If the Inverter capacity is 0.75 kW and the motor capacity is 0.4 kW, the torque limit set value for
α
=
200%, calculated with the above formula, is as follows: Torque limit set value (b041 to b044) =
α
×
(Motor capacity) / (Inverter capacity) = 200% x (0.4 kW)/(0.75 kW) = 106%
0-Hz Sensorless Vector Control
• This function enables high-torque operation in the 0-Hz range (0- to 3-Hz frequency reference).
This control method is particularly suitable for applications such as an elevating system, which
requires sufficient torque in a low-frequency range at startup (e.g. crane, hoist).
• To use this function, set V/f characteristics selection A044/A244 to "04".
• To use this function, make sure that the motor parameter settings are suitable for your motor.
(Refer to "Motor Parameter Selection" (page 4-112).)
• The parameters for 0-Hz SLV control are as follows:
• In 0-Hz limit H060/H260, you can set a current value used for constant current control in the 0-
Hz range (generally, 3.0 Hz or lower). This parameter is expressed as a ratio of the output current
to the Inverter's rated current.
• In 0-Hz SLV startup boost amount H061/H261, you can set a current boost amount at startup in
the 0-Hz range. A current value expressed as a ratio to the Inverter's rated current is added to
the current value set in H060/H260 at startup only.
• Note the following before use:
• Select an Inverter with one rank higher in capacity than the motor's.
• Sufficient characteristics may not be obtained if you select a motor size two or more ranks lower
than the maximum applicable motor size.
• In the 0-Hz sensorless control mode, the digital command board (3GAX-DI01) cannot be used.
Parameter No.
Function name
Data
Default setting
Unit
H060/H260
Limit at 0 Hz
0.0 to 100.0:
Current limit in low frequency range
100.0
%
H061/H261
Boost amount at SLV
startup, 0 Hz
0. to 50.: Current boost amount at startup
50.
%
Содержание 3G3RX Series
Страница 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Страница 2: ......
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Страница 22: ......
Страница 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Страница 48: ......
Страница 108: ......
Страница 324: ......
Страница 325: ...Chapter 5 Maintenance Operations 5 1 Protective Functions and Troubleshooting 5 1 5 2 Warning Function 5 10 ...
Страница 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Страница 348: ......
Страница 349: ...Chapter 7 Specifications 7 1 Standard Specification List 7 1 7 2 Dimensional Drawing 7 6 7 3 Options 7 14 ...
Страница 358: ...7 9 7 2 Dimensional Drawing 7 Specifications 3G3RX A2300 A4300 368 79 265 310 10 510 540 2 φ10 195 45 80 265 ...
Страница 360: ...7 11 7 2 Dimensional Drawing 7 Specifications 3G3RX A2550 380 670 700 2 φ12 12 380 480 250 352 79 ...
Страница 361: ...7 12 7 2 Dimensional Drawing 7 Specifications 3G3RX A4750 A4900 2 φ12 2 12 300 390 268 700 79 670 357 ...
Страница 362: ...7 13 7 2 Dimensional Drawing 7 Specifications 3G3RX A411K A413K 2 φ12 2 12 380 480 270 740 79 710 480 ...
Страница 369: ...7 20 7 3 Options 7 Specifications 3G3AX RBC4001 3G3AX RBC6001 100 150 280 300 5 70 100 70 150 390 410 5 ...
Страница 392: ......
Страница 393: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 41 Appendix 3 Life Alarm Output App 42 ...
Страница 436: ......
Страница 437: ...Index ...
Страница 441: ......