6-13
Acknowledging and Setting Alarms
6
6.4 Setting the Auxiliary Alarm Function (Basic Setting Mode)
Hold/non-hold operation of the alarm output relay
When the alarm changes from an ON state to the OFF state, you can select to
• Turn OFF the output relay in sync with the alarm release (non-hold)
• Turn OFF the output relay with an alarm acknowledge operation (hold)
This applies to all alarm output relays. The initial setting is set to [Nonhold].
• When set to non-hold
Alarm on
Alarm off
Relay output on
*
Relay output off
* Shows the status of the normally-opened
(NO) contact of the relay. The status is the
reverse for the normally-closed contact.
• When set to hold
Press Alarm
ACK
key
Alarm on
Alarm off
Relay output on
*
Relay output off
Note
If the reflash alarm is turned ON, I01 to I03 are set to non-hold. Specifying hold produces no
effect.
Hold/non-hold of the alarm indicator
When the alarm changes from the activated state to the released state, you can select to
• release the alarm indicator in sync with the alarm release (non-hold)
• release the alarm indicator with an alarm acknowledge operation (hold)
The initial setting is [Nonhold].
For details regarding the alarm indicator, see section 6.1.
Содержание RD-MV100 Series
Страница 40: ...1 22 This page intentionally left blank...
Страница 41: ...1 23 Overview of Functions 1 This page intentionally left blank...
Страница 139: ...7 5 Setting and Operating the Display 7 This page intentionally left blank...
Страница 140: ...7 6 This page intentionally left blank...
Страница 215: ...10 15 Other Functions 10 This page intentionally left blank...
Страница 216: ...10 16 This page intentionally left blank...
Страница 217: ...10 17 Other Functions 10 This page intentionally left blank...
Страница 218: ...10 18 This page intentionally left blank...
Страница 219: ...10 19 Other Functions 10 This page intentionally left blank...