Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
Assigning Ground-Fault Alarm and Trip Levels
The Setup|G.F. window allows you to set the alarm and trip levels.
Tap the G.F. button to access the Setup|G.F. window.
Fig. 3.49
Setup|G.F. window (Fuel Oil Ambient Control)
Input the Ground-Fault Alarm and Ground-Fault Trip:
Ground-Fault Alarm:
When the ground-fault current exceeds this level the ACS-UIT2 goes in alarm.
Range:
10–200 mA
Default:
20 mA
Ground-Fault Alarm:
When the ground-fault current exceeds this level the ACS-PCM2-5 turns off
the circuit relay.
Range:
10–200 mA
Default:
30 mA
Assigning Circuit Voltage
The Setup|Voltage window allows you to set the circuit voltage used to calculate the energy
consumption of the circuit.
Fig. 3.50
Setup|Voltage (Fuel Oil Ambient Control)