nVent.com
|
13
Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
LC = Line current
GF = Ground fault
ACS-PCM2-5 / Circuit #
1
LC
GF
Output
Relay 1
Local/A
RTD
2
LC
GF
Output
Relay 2
Local
RTD
3
LC
GF
Output
Relay 3
Local
RTD
4
LC
GF
Output
Relay 4
Local
RTD
5
LC
GF
Output
Relay 5
Local
RTD
Additional RTDs
ACS-UIT2
B #1
C 2
D 3
4
5
6
7
8
RS-485
RMM2
Fig. 1.4
Multiple RTD input control circuit
A circuit may also be controlled by multiple RTD inputs by adding a RMM2 module to the network.
Multiple RTDs may be used for control or monitoring of a heating circuit.
1
LC
GF
Output
Relay 1
Local/A
RTD
2
LC
GF
Output
Relay 2
Local
RTD
3
LC
GF
Output
Relay 3
Local
RTD
4
LC
GF
Output
Relay 4
Local
RTD
5
LC
GF
Output
Relay 5
Local
RTD
B #1
C 2
D 3
4
5
6
7
8
RMM2
1
LC
GF
Output
Relay 1
Local/A
RTD
Local/A RTD
Local/B RTD
2
LC
GF
Output
Relay 2
Local
RTD
3
LC
GF
Output
Relay 3
Local
RTD
4
LC
GF
Output
Relay 4
Local
RTD
5
LC
GF
Output
Relay 5
Local
RTD
ACS-PCM2-5
/ Circuit #
ACS-PCM2-5
/ Circuit #
Additional
RTDs
RS-485
RS-485
ACS-UIT2
C910-485
RS-485
RS-485
Fig. 1.5
Multiple ACS-PCMs, C910-485 and RMM2
More advanced systems can have multiple heating circuits sharing RTDs for control and monitoring.
Содержание RAYCHEM ACS-30
Страница 1: ...nVent com 1 Raychem AR H58692 ACS30UIT2Programming EN 1805 PROGRAMMING GUIDE ACS 30 System...
Страница 2: ...nVent com 2 Raychem AR H58692 ACS30UIT2Programming EN 1805...
Страница 139: ...nVent com 139 Raychem AR H58692 ACS30UIT2Programming EN 1805 Fig 5 14 ACS 30 Program Integrator Printout...
Страница 144: ...nVent com 144 Raychem AR H58692 ACS30UIT2Programming EN 1805...