ASSIGNING TEMPERATURE ALARMS
Once RTDs have been assigned to the monitoring circuit high and low temperature alarms may be
set. Tap the Alarm tab
Fig. 4.5
Temperature Monitor - Setup|Alarms
High Temperature Alarm:
If any RTD assigned to the temperature monitor circuit measures a
temperature above this threshold, the ACS-UIT2 generates an alarm. The limit can be set for any
temperature values you desire for your application within the range allowed.
Range:
Low Temp–400ºF (204ºC)
Default:
200ºF (88ºC)
Low Temp Alarm:
If any RTD assigned to the temperature monitor circuit measures a temperature
below this threshold, the ACS-UIT2 generates an alarm.
Range:
99ºF (-40ºC) to High temp alarm
Default:
-40ºF (-40ºC)
Temperature Alarm Filter:
This minimizes nuisance alarms by forcing the ACS-UIT2 to verify that
the alarm condition continually exists for over the selected period of time before alarming.
Range:
0–999 minutes
Default:
15 minutes
Note:
Setting the Alarm Filter to 0 minutes is mainly for testing and demonstration purposes.
Selecting this option for normal use may cause nuisance alarming since this option may not allow
the ACS-UIT2 time to verify that the alarm condition exists.
Содержание RAYCHEM ACS-30
Страница 1: ...nVent com 1 Raychem AR H58692 ACS30UIT2Programming EN 1805 PROGRAMMING GUIDE ACS 30 System...
Страница 2: ...nVent com 2 Raychem AR H58692 ACS30UIT2Programming EN 1805...
Страница 139: ...nVent com 139 Raychem AR H58692 ACS30UIT2Programming EN 1805 Fig 5 14 ACS 30 Program Integrator Printout...
Страница 144: ...nVent com 144 Raychem AR H58692 ACS30UIT2Programming EN 1805...