Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
3.8.2.
TEMP CONTROL – AMBIENT TEMPERATURE CONTROL
Fig. 3.78
Roof & Gutter - Ambient Temperature Control Window
The Ambient Temperature window allows you to control your Roof & Gutter application using
ambient temperature. Tap Ambient Control
Fig. 3.79
Setup|Roof & Gutter - Ambient Temp Control Window
Setpoint:
Enter the temperature setpoint for ambient control
Range:
30°F (-1°C)–50°F (10°C)
Default:
35ºF (2°C)
Deadband:
If the measured temperature is above the ambient or high temperature override setpoint
temperature plus deadband, the relay output is turned off. If the control temperature is below the
setpoint temperature, the output is turned on.
Range:
1°F (1°C)–10°F (5°C)
Default: 5ºF (3°C)
High Temperature Override:
The high temperature override is the setpoint that will override the
ambient control temperature. This is typically used as a gutter sensor.
Range:
40°F (4°C)–90°F (32°C)
Default:
55ºF (13°C)