Assigning RTDs in Monitor only mode
The same process is used to assign RTDs to Monitor Only mode. Any RTD in the system can be
assigned whether from a ACS-PCM2-5 relay number or from a RMM2 module. Theses RTDs do not
have any control function associated with them, however, they can be assigned alarm values.
Assigning additional RTDs to a circuit
RTDs can be assigned to a circuit from ACS-CRM boards or RMM2 modules. To assign the
additional RTDs to a circuit enter the device address and RTD number as listed under your
Network|Device window.
Fig. 2.18
Assigning additional RTDs.
2.2.4.
SETUP|ALARM
The Setup|Alarms window lists all of the temperature alarm conditions for line control/monitoring.
The minimum and maximum values for each alarm condition are included for each application
control mode in Section 3.
Fig. 2.19 Setup|Alarms window
2.2.5.
SETUP|G.F.
The Setup|G.F. window configures ground-fault alarm and trip values for the circuit. The alarm/trip
conditions are latching and must be manually reset.